[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974155":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},974155,704,1,"单选题","剩余电流式电气火灾监控探测器的报警设定值范围应为（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","50-500mA",false,{"key":16,"text":17,"correct":14},"B","20-500mA",{"key":19,"text":20,"correct":14},"C","50-1000mA",{"key":22,"text":23,"correct":24},"D","20-1000mA",true,"当被保护线路剩余电流达到报警设定值（可自行设定，要求设定范围在20~1000mA）时，剩余电流式电气火灾监控探测器应能在30s内发出报警信号，点亮报警指示灯，向电气火灾监控设备发送报警信号。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]