[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974094":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974094,704,2,"多选题","下列关于自动喷水灭火系统报警阀组在准工作状态下的要求说法正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","湿式报警阀系统标识清晰，组件齐全，外观完好",true,{"key":16,"text":17,"correct":18},"B","主阀前后压力指示正常，表差＜0.02MPa，各项测试功能正常，排水正常报警阀、压力开关、水力警铃等动作正常",false,{"key":20,"text":21,"correct":14},"C","距水力警铃3m远处的警铃声强应不低于70dB",{"key":23,"text":24,"correct":14},"D","干式和预作用系统报警阀还应充气装置启停准确，充气压力值符合设计要求",{"key":26,"text":27,"correct":14},"E","加速排气装置排气速度正常，电磁阀动作灵敏间前稳压值符合设计要求","ACDE","自动喷水灭火系统报警阀组的准工作状态要求：湿式报警阀系统标识清晰，组件齐全，外观完好；主阀前后压力指示正常，表差＜0.01MPa，各项测试功能正常，排水正常，报警阀、压力开关、水力警铃等动作正常，距水力警铃3m远处的警铃声强应不低于70dB；干式和预作用系统报警阀还应充气装置启停准确，充气压力值符合设计要求，加速排气装置排气速度正常，电磁阀动作灵敏，阀前稳压值符合设计要求。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]