[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974062":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},974062,704,1,"单选题","下列关于测温式电气火灾监控探测器的设置说法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","是检测高压配电线路中线路温度的电气火灾监控探测器",true,{"key":16,"text":17,"correct":18},"B","应设置在电缆接头、端子、重点发热部件等部位",false,{"key":20,"text":21,"correct":18},"C","保护对象为1000V及以下的配电线路，测温式电气火灾监控探测器应采用接触式布置",{"key":23,"text":24,"correct":18},"D","保护对象为1000V以上的供电线路，测温式电气火灾监控探测器宜选择光栅光纤测温式或红外测温式电气火灾监控探测器","测温式电气火灾监控探测器是检测低压配电线路中线路温度的电气火灾监控探测器，应设置在电缆接头、端子、重点发热部件等部位。保护对象为1000V及以下的配电线路，测温式电气火灾监控探测器应采用接触式布置；保护对象为1000V以上的供电线路，测温式电气火灾监控探测器宜选择光栅光纤测温式或红外测温式电气火灾监控探测器，光栅光纤测温式电气火灾监控探测器应直接设置在保护对象的表面。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]