[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-973666":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},973666,704,1,"单选题","（）在水流作用下动作，并通过信号模块向火灾自动报警系统发出报警信号，通报位置分区。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","压力开关",false,{"key":16,"text":17,"correct":14},"B","报警阀",{"key":19,"text":20,"correct":21},"C","水流指示器",true,{"key":23,"text":24,"correct":14},"D","末端试水装置","系统正常工作状态是指火灾发生时洒水喷头动作喷水以及日常开展各种功能检查和测试等工作时的状态。当系统处于不同工作情形时，系统各组件的工作状态也不同。如火灾时：（1）受高温烟气作用喷头动作喷水，且出水压力不低于0.05MPa（2）水流指示器在水流作用下动作，并通过信号模块向火灾自动报警系统发出报警信号，通报位置分区。（3）报警阀开启，打通输水通道；水力警铃动作并发出声报警信号，该声响在3m远处不低于70dB；压力开关动作，连锁启动消防水泵，并向火灾自动报警系统发出压力开关动作信号。（4）消防水泵启动，向自动喷水灭火系统管网供水。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]