[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-973300":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},973300,704,2,"多选题","湿式报警阀组报警功能的测试途径（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","电磁阀",false,{"key":16,"text":17,"correct":18},"B","末端试水装置测试",true,{"key":20,"text":21,"correct":18},"C","报警阀泄水阀测试",{"key":23,"text":24,"correct":18},"D","利用警铃试验阀测试","BCD","湿式报警阀组报警功能可通过末端试水装置、专用测试管路、报警阀泄水阀、警铃试验阀等途径进行测试，如图5-2_9所示。不同测试途径，受影响的组件也不同：利用末端试水装置测试时，水流指示器动作，报警阀阀瓣打开，水力警铃动作，压力开关动作，消防水泵启动。利用专用测试管路和报警阀泄水阀测试时，报警阀阀瓣打开，水力警铃动作，压力开关动作，消防水泵启动。利用警铃试验阀测试时，水力警铃动作，压力开关动作，消防水泵启动。",{"id":6,"name":28,"category":29,"favorite":30},"中级技能","建筑工程",0]