[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-973189":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":24,"analysis":25},973189,704,2,"多选题","对于可能造成无法通过消防水泵接合器向室内管网供水的原因，维修方法有（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","釆取可靠的防冻措施",true,{"key":16,"text":17,"correct":14},"B","非施工安装或维修作业，水泵接合器控制阀必须完全打开",{"key":19,"text":20,"correct":14},"C","按正确方向重新安装止回阀",{"key":22,"text":23,"correct":14},"D","正确设置给水系统和分区标识，根据拟供水系统正确选择消防水泵接合器","ABCD","无法通过消防水泵接合器向室内管网供水的原因有：(1)止回阀安装方向错误。(2)控制阀被误关闭。(3)严寒地区防冻措施不到位致使阀门或管内水冻结。（4）消防水泵接合器选择错误或所属给水系统和分区标识不正确。对应的维修方法是：按正确方向重新安装止回阀，非施工安装或维修作业，水泵接合器控制阀必须完全打开，釆取可靠的防冻措施，正确设置给水系统和分区标识，根据拟供水系统正确选择消防水泵接合器。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]