[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-971913":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},971913,703,2,"多选题","下列通风、空气调节系统的风管部位应设置公称动作温度为70℃的防火阀的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","穿越防火分区处",true,{"key":16,"text":17,"correct":14},"B","穿越通风、空气调节机房的房间隔墙和楼板处",{"key":19,"text":20,"correct":14},"C","穿越重要或火灾危险性大的场所的房间隔墙和楼板处",{"key":22,"text":23,"correct":24},"D","建筑内每个防火分区的通风、空气调节系统均独立设置，水平风管与竖向总管的交接处",false,{"key":26,"text":27,"correct":14},"E","竖向风管与每层水平风管交接处的水平管段上","ABCE","防火阀的设置部位。下列部位应设置防火阀。通风、空气调节系统的风管在下列部位应设置公称动作温度为70℃的防火阀：穿越防火分区处；穿越通风、空气调节机房的房间隔墙和楼板处；穿越重要或火灾危险性大的场所的房间隔墙和楼板处；穿越防火分隔处的变形缝两侧；竖向风管与每层水平风管交接处的水平管段上。当建筑内每个防火分区的通风、空气调节系统均独立设置时，水平风管与竖向总管的交接处可不设置防火阀。",{"id":6,"name":31,"category":32,"favorite":33},"基础知识（通用）","建筑工程",0]