[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-971907":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},971907,703,2,"多选题","下列情况应设置消防水池（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","当生产、生活用水量达到最大时，市政给水管网或入户引入管不能满足室内、室外消防给水设计流量",true,{"key":16,"text":17,"correct":18},"B","当生产、生活用水量达到最小时，市政给水管网或入户引入管不能满足室内、室外消防给水设计流量",false,{"key":20,"text":21,"correct":14},"C","当采用一路消防供水或只有一条入户引入管，且室外消火栓设计流量大于20L\u002Fs或建筑高度大于50m时",{"key":23,"text":24,"correct":14},"D","市政消防给水设计流量小于建筑室内外消防给水设计流量",{"key":26,"text":27,"correct":18},"E","市政消防给水设计流量大于建筑室内外消防给水设计流量","ACD","消防水池。消防水池是人工建造的供固定或移动消防水泵吸水的储水设施，是建筑消防中十分重要的水源。符合下列规定之一时，应设置消防水池：一是当生产、生活用水量达到最大时，市政给水管网或入户引入管不能满足室内、室外消防给水设计流量；二是当采用一路消防供水或只有一条入户引入管，且室外消火栓设计流量大于20L\u002Fs或建筑高度大于50m时；三是市政消防给水设计流量小于建筑室内外消防给水设计流量。",{"id":6,"name":31,"category":32,"favorite":33},"基础知识（通用）","建筑工程",0]