[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-971782":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},971782,703,2,"多选题","下列关于防护区开口的设置说法符合规范规定的有（ ）",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","防护区开口的设置，为防止灭火剂流失，防护区的围护构件上不宜设置敞开孔洞",true,{"key":16,"text":17,"correct":14},"B","当必须设置敞开孔洞时，应设置能手动和自动关闭装置",{"key":19,"text":20,"correct":14},"C","喷放灭火剂前，防护区内除泄压口外的开口应能自行关闭",{"key":22,"text":23,"correct":24},"D","采用全淹没二氧化碳灭火系统扑救气体、液体、电气火灾和固体表面火灾时，在喷放二氧化碳前不能自动关闭的开口，其面积不应大于防护区总内表面积的5%，且开口不应设在底面",false,{"key":26,"text":27,"correct":24},"E","启动释放气体灭火剂之后，必须切断可燃、助燃气体的气源","ABC","防护区开口的设置，为防止灭火剂流失，防护区的围护构件.上不宜设置敞开孔洞；当必须设置敞开孔洞时，应设置能手动和自动关闭装置。喷放灭火剂前，防护区内除泄压口外的开口应能自行关闭。采用全淹没二氧化碳灭火系统扑救气体、液体、电气火灾和固体表面火灾时，在喷放二氧化碳前不能自动关闭的开口，其面积不应大于防护区总内表面积的3%，且开口不应设在底面；启动释放气体灭火剂之前或同时，必须切断可燃、助燃气体的气源。",{"id":6,"name":31,"category":32,"favorite":33},"基础知识（通用）","建筑工程",0]