[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-971768":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},971768,703,1,"单选题","下列关于气体灭火系统防火区的设置说法不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","防护区宜以单个封闭空间划分",false,{"key":16,"text":17,"correct":14},"B","采用管网灭火系统时，一个防护区面积不宜大于800㎡，且容积不宜大于3600m3",{"key":19,"text":20,"correct":14},"C","采用预制灭火系统时，一个防护区面积不宜大于500㎡，且容积不宜大于1600m3",{"key":22,"text":23,"correct":24},"D","同一区间的吊顶层和地板下需同时保护时，应分别设置防护区",true,"防护区宜以单个封闭空间划分，同一区间的吊顶层和地板下需同时保护时，可合为一个防护区；采用管网灭火系统时，一个防护区面积不宜大于800㎡，且容积不宜大于3600m3；采用预制灭火系统时，一个防护区面积不宜大于500㎡，且容积不宜大于1600m3。",{"id":6,"name":27,"category":28,"favorite":29},"基础知识（通用）","建筑工程",0]