[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-971608":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},971608,703,2,"多选题","电容器运行中常见的故障有渗漏油、鼓肚和喷油等。下列属于其防火措施的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","防止过电压，运行电压不超过1.2倍的额定电压，运行电流不宜超过1.4倍的额定电流",false,{"key":16,"text":17,"correct":14},"B","保持良好的通风条件，室内温度不宜超过50%",{"key":19,"text":20,"correct":21},"C","加强维护，做到无鼓肚、渗漏油、套管松动和裂损、火花放电等不良现象",true,{"key":23,"text":24,"correct":21},"D","接地线要连接良好",{"key":26,"text":27,"correct":21},"E","设置可靠的保护装置。用熔断器保护时，熔断器的额定电流不应大于电容器额定电流的1.3倍。","CDE","电容器运行中常见的故障有渗漏油、鼓肚和喷油等。其防火措施有： （1）防止过电压。运行电压不超过1.1倍的额定电压，运行电流不宜超过1.3倍的额定电流。 （2）保持良好的通风条件，室内温度不宜超过40%。 （3）加强维护，做到无鼓肚、渗漏油、套管松动和裂损、火花放电等不良现象。 （4）接地线要连接良好。 （5）设置可靠的保护装置。用熔断器保护时，熔断器的额定电流不应大于电容器额定电流的1.3倍。对于供高压开关试验用的电容器堆，由于电容器数量多，总油量大，占地面积和空间大，所以一且发生火灾，扑救工作困难，造成的损失大。 因此，除采取上述措施外，还应设置适于扑灭电气火灾的固定灭火装置。",{"id":6,"name":31,"category":32,"favorite":33},"基础知识（通用）","建筑工程",0]