[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-971607":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},971607,703,2,"多选题","下列关于过负载保护电器的动作特性说法正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","线路计算电流小于等于熔断器熔体额定电流，后者应小于等于导体允许持续载流量",true,{"key":16,"text":17,"correct":18},"B","保证保护电器可靠动作的电流小于等于1.25倍熔断器熔体额定电流",false,{"key":20,"text":21,"correct":14},"C","保证保护电器可靠动作的电流小于等于1.45倍熔断器熔体额定电流",{"key":23,"text":24,"correct":18},"D","过负载保护电器的熔断必须小于漏大电流",{"key":26,"text":27,"correct":18},"E","接地故障保护电器的选择应根据供配电系统的接地形式、电气设备使用特点及导体截面等确定","AC","过负载保护电器的动作特性应同时满足以下两个条件： （1）线路计算电流小于等于熔断器熔体额定电流，后者应小于等于导体允许持续载流量。 （2）保证保护电器可靠动作的电流小于等于1.45倍熔断器熔体额定电流。当保护电器为断路器时，保证保护电器可靠动作的电流为约定时间内的约定动作电流；当保护电器为熔断器时，保证保护电器可靠动作的电流为约定时间内的熔断电流。",{"id":6,"name":31,"category":32,"favorite":33},"基础知识（通用）","建筑工程",0]