[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-971332":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},971332,703,1,"单选题","某四星级酒店建筑高度为52m，建筑内全部设置自动喷水灭火系统。酒店每层设置两部疏散楼梯，布置在走廊的两端，该建筑内位于两个安全出口之间的房间门至最近安全出口的最大直线距离为（ ）m。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","30",false,{"key":16,"text":17,"correct":18},"B","37.5",true,{"key":20,"text":21,"correct":14},"C","40",{"key":23,"text":24,"correct":14},"D","50","公共建筑直通疏散走道的房间疏散门至最近安全出口的直线距离应符合表的规定。 注：（1）建筑内开向敞开式外廊的房间疏散门至最近安全出口的直线距离可按本表的规定增加5m。 （2）直通疏散走道的房间疏散门至最近敞开楼梯间的直线距离，当房间位于两个楼梯间之间时，应按本表的规定减少5m；当房间位于袋形走道两侧或尽端时，应按本表的规定减少2m。 （3）建筑内全部设置自动喷水灭火系统时，其安全疏散距离可按本表的规定增加25%。",{"id":6,"name":27,"category":28,"favorite":29},"基础知识（通用）","建筑工程",0]