[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-968239":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},968239,702,2,"多选题","下列柴油发电机房布置在民用建筑内时，说法符合规范规定的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","应布置在人员密集场所的上一层、下一层或贴邻",false,{"key":16,"text":17,"correct":18},"B","宜布置在首层或地下一、二层",true,{"key":20,"text":21,"correct":14},"C","距离通向屋面的安全出口不应小于6m",{"key":23,"text":24,"correct":18},"D","不应布置在人员密集场所的上一层、下一层或贴邻",{"key":26,"text":27,"correct":18},"E","应采用耐火极限不低于2.00h的防火隔墙和1.50h的不燃性楼板与其他部位分隔，门应采用甲级防火门","BDE","柴油发电机房布置在民用建筑内时应满足： （1）宜布置在首层或地下一、二层； （2）不应布置在人员密集场所的上一层、下一层或贴邻； （3）应采用耐火极限不低于2.00h的防火隔墙和1.50h的不燃性楼板与其他部位分隔，门应釆用甲级防火门。",{"id":6,"name":31,"category":32,"favorite":33},"基础知识（通用）","建筑工程",0]