[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-701-9":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":611},{"id":5,"name":6,"category":7,"favorite":8},701,"高级技能","建筑工程",0,9,50,2716,[13,34,46,58,70,82,94,106,118,130,142,154,165,177,189,201,212,224,232,244,256,268,278,289,301,313,325,337,349,361,373,385,397,409,421,433,445,457,469,480,492,504,516,528,539,551,563,575,587,599],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":24,"analysis":33},964613,1,"单选题","测试报警阀密封性，试验压力为额定工作压力的（ ）倍的静水压力，保压时间不小于5min后，阀瓣处无渗透。",[19,23,27,30],{"key":20,"text":21,"correct":22},"A","l",false,{"key":24,"text":25,"correct":26},"B","2",true,{"key":28,"text":29,"correct":22},"C","3",{"key":31,"text":32,"correct":22},"D","4","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":28,"analysis":33},964614,"同时使用信号阀和水流指示器控制的自动喷水灭火系统，信号阀安装在水流指示器前的管道上，与水流指示器间的距离不小于（ ）mm。",[38,40,42,44],{"key":20,"text":39,"correct":22},"100",{"key":24,"text":41,"correct":22},"200",{"key":28,"text":43,"correct":26},"300",{"key":31,"text":45,"correct":22},"500",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":31,"analysis":33},964615,"湿式喷水灭火系统、干式喷水灭火系统的自动联动触发信号是（ ）信号，由消防联动控制器按照预设逻辑完成自动灭火的控制。",[50,52,54,56],{"key":20,"text":51,"correct":22},"水流动作",{"key":24,"text":53,"correct":22},"感探测器",{"key":28,"text":55,"correct":22},"信号阀动作",{"key":31,"text":57,"correct":26},"报警阀的压力开关动作",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":31,"analysis":33},964616,"干式报警阀应（ ）至少进行一次报警阀正确运行验证试验。",[62,64,66,68],{"key":20,"text":63,"correct":22},"每月",{"key":24,"text":65,"correct":22},"每季度",{"key":28,"text":67,"correct":22},"每半年",{"key":31,"text":69,"correct":26},"每年",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":31,"analysis":33},964617,"泡沫产生器主要由壳体组、（ ）和导板组三部分组成。",[74,76,78,80],{"key":20,"text":75,"correct":22},"滤网",{"key":24,"text":77,"correct":22},"产生器密封玻璃",{"key":28,"text":79,"correct":22},"引流管",{"key":31,"text":81,"correct":26},"泡沫喷管组",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":24,"analysis":33},964618,"对有囊式泡沫罐，应每（ ）个月做一次胶囊验漏试验。",[86,88,90,92],{"key":20,"text":87,"correct":22},"3个月",{"key":24,"text":89,"correct":26},"6个月",{"key":28,"text":91,"correct":22},"12个月",{"key":31,"text":93,"correct":22},"24个月",{"id":95,"libraryId":5,"type":15,"typeLabel":16,"stem":96,"options":97,"answer":20,"analysis":33},964619,"移动式泡沫系统系统适用于总储量小于200m3、单罐储量不大于100m3、且罐高不大于（ ）的地上水溶性甲、乙、丙类液体立式储罐。",[98,100,102,104],{"key":20,"text":99,"correct":26},"5米",{"key":24,"text":101,"correct":22},"6米",{"key":28,"text":103,"correct":22},"7米",{"key":31,"text":105,"correct":22},"8米",{"id":107,"libraryId":5,"type":15,"typeLabel":16,"stem":108,"options":109,"answer":28,"analysis":33},964620,"氟蛋白泡沫灭火剂抗烧时间是（ ）min。",[110,112,114,116],{"key":20,"text":111,"correct":22},"≥6",{"key":24,"text":113,"correct":22},"≥9",{"key":28,"text":115,"correct":26},"≥12",{"key":31,"text":117,"correct":22},"≥5",{"id":119,"libraryId":5,"type":15,"typeLabel":16,"stem":120,"options":121,"answer":24,"analysis":33},964621,"泡沫灭火系统在实施灭火各个阶段的全部联动控制信号均应由（ ）发出。",[122,124,126,128],{"key":20,"text":123,"correct":22},"消防联动控制器",{"key":24,"text":125,"correct":26},"泡沫灭火控制器",{"key":28,"text":127,"correct":22},"火灾报警控制器",{"key":31,"text":129,"correct":22},"手动报警按钮",{"id":131,"libraryId":5,"type":15,"typeLabel":16,"stem":132,"options":133,"answer":24,"analysis":33},964622,"水成膜泡沫灭火剂灭火时间是（ ）s。",[134,136,138,140],{"key":20,"text":135,"correct":22},"≤30",{"key":24,"text":137,"correct":26},"≤40",{"key":28,"text":139,"correct":22},"≤50",{"key":31,"text":141,"correct":22},"≤60",{"id":143,"libraryId":5,"type":15,"typeLabel":16,"stem":144,"options":145,"answer":31,"analysis":33},964623,"高倍数泡沫灭火系统分为全淹没式、局部应用式（ ）三种类型。",[146,148,150,152],{"key":20,"text":147,"correct":22},"卧式",{"key":24,"text":149,"correct":22},"立式",{"key":28,"text":151,"correct":22},"橫式",{"key":31,"text":153,"correct":26},"移动式",{"id":155,"libraryId":5,"type":15,"typeLabel":16,"stem":156,"options":157,"answer":24,"analysis":33},964624,"环泵式泡沫比例混合器吸液口不应高出泡沫液储罐最低液面（ ），否则泡沫混合液的混合比难以保证。",[158,160,162,164],{"key":20,"text":159,"correct":22},"0.5",{"key":24,"text":161,"correct":26},"l0",{"key":28,"text":163,"correct":22},"1.5",{"key":31,"text":25,"correct":22},{"id":166,"libraryId":5,"type":15,"typeLabel":16,"stem":167,"options":168,"answer":24,"analysis":33},964625,"消防干粉泡灭火系统适用于液化石油气、天然气等可燃气体火灾的扑救，在（ ）场所不适用。",[169,171,173,175],{"key":20,"text":170,"correct":22},"油船油库",{"key":24,"text":172,"correct":26},"飞机维修库",{"key":28,"text":174,"correct":22},"输油码头",{"key":31,"text":176,"correct":22},"机场机库",{"id":178,"libraryId":5,"type":15,"typeLabel":16,"stem":179,"options":180,"answer":31,"analysis":33},964626,"对消防水泡灭火系统工作原理描述不正确的是：（ ）。",[181,183,185,187],{"key":20,"text":182,"correct":22},"火灾发生时，开启消防泵组及管路阀门",{"key":24,"text":184,"correct":22},"消防水经消防泵加压获得的静压能，在消防泡喷喷处转换为动能",{"key":28,"text":186,"correct":22},"高速水流由喷嘴射向火源",{"key":31,"text":188,"correct":26},"能够隔绝空气使其窒息",{"id":190,"libraryId":5,"type":15,"typeLabel":16,"stem":191,"options":192,"answer":20,"analysis":33},964627,"（ ）对近距离的火灾有更好的扑救效果。",[193,195,197,199],{"key":20,"text":194,"correct":26},"消防水泡灭火系统",{"key":24,"text":196,"correct":22},"消防泡沫泡灭火系统",{"key":28,"text":198,"correct":22},"消防干粉泡灭火系统",{"key":31,"text":200,"correct":22},"消防气体泡灭火系统",{"id":202,"libraryId":5,"type":15,"typeLabel":16,"stem":203,"options":204,"answer":31,"analysis":33},964628,"消防泡沫泡灭火系统工作原理不正确的是：（ ）。",[205,206,208,210],{"key":20,"text":182,"correct":22},{"key":24,"text":207,"correct":22},"消防压力水流经泡沫混合装置时按照一定的比例与泡沫原液混合，形成泡沫混合液，并在消防泡喷嘴处以高速射流喷出",{"key":28,"text":209,"correct":22},"泡沫混合液射流在消防泡喷嘴处及空中卷吸入空气，与空气混合、发泡形成空气泡沫液",{"key":31,"text":211,"correct":26},"空气泡沫液被投射到火源根部灭火",{"id":213,"libraryId":5,"type":15,"typeLabel":16,"stem":214,"options":215,"answer":24,"analysis":33},964629,"消防干粉泡灭火系统的灭火机理是（ ）。",[216,218,220,222],{"key":20,"text":217,"correct":22},"隔氧阻燃",{"key":24,"text":219,"correct":26},"切割火焰、破坏燃烧链",{"key":28,"text":221,"correct":22},"阻隔辐射热",{"key":31,"text":223,"correct":22},"吸热冷却",{"id":225,"libraryId":5,"type":15,"typeLabel":16,"stem":226,"options":227,"answer":20,"analysis":33},964630,"（ ）能够隔绝空气并冷却燃烧物，起到迅速扑灭或抑制火灾的作用。",[228,229,230,231],{"key":20,"text":194,"correct":26},{"key":24,"text":196,"correct":22},{"key":28,"text":198,"correct":22},{"key":31,"text":200,"correct":22},{"id":233,"libraryId":5,"type":15,"typeLabel":16,"stem":234,"options":235,"answer":31,"analysis":33},964631,"下面哪项不是消防水泡灭火系统的组成部分？（ ）",[236,238,240,242],{"key":20,"text":237,"correct":22},"消防水泡",{"key":24,"text":239,"correct":22},"控制装置",{"key":28,"text":241,"correct":22},"消防水泵",{"key":31,"text":243,"correct":26},"稳压装置",{"id":245,"libraryId":5,"type":15,"typeLabel":16,"stem":246,"options":247,"answer":28,"analysis":33},964632,"消防水泡的形式不包括（ ）。",[248,250,252,254],{"key":20,"text":249,"correct":22},"手动式",{"key":24,"text":251,"correct":22},"电控式",{"key":28,"text":253,"correct":26},"电-粉控式",{"key":31,"text":255,"correct":22},"电-气控式",{"id":257,"libraryId":5,"type":15,"typeLabel":16,"stem":258,"options":259,"answer":28,"analysis":33},964633,"哪种不是控制装置的形式？（ ）",[260,262,264,266],{"key":20,"text":261,"correct":22},"立式控制柜",{"key":24,"text":263,"correct":22},"台式控制柜",{"key":28,"text":265,"correct":26},"卧式控制柜",{"key":31,"text":267,"correct":22},"无线遥控装置",{"id":269,"libraryId":5,"type":15,"typeLabel":16,"stem":270,"options":271,"answer":20,"analysis":33},964634,"消防泡沫泡灭火系统由（ ）等组成。",[272,273,274,276],{"key":20,"text":237,"correct":26},{"key":24,"text":241,"correct":22},{"key":28,"text":275,"correct":22},"泡沫液储罐",{"key":31,"text":277,"correct":22},"泡沫比例混合装置",{"id":279,"libraryId":5,"type":15,"typeLabel":16,"stem":280,"options":281,"answer":31,"analysis":33},964635,"哪一项不是消防干粉泡灭火系统的组成部分？（ ）",[282,284,286,288],{"key":20,"text":283,"correct":22},"消防干粉泡",{"key":24,"text":285,"correct":22},"干粉储罐",{"key":28,"text":287,"correct":22},"氮气瓶组",{"key":31,"text":241,"correct":26},{"id":290,"libraryId":5,"type":15,"typeLabel":16,"stem":291,"options":292,"answer":31,"analysis":33},964636,"水喷雾灭火系统的组成部件不包括（ ）。",[293,295,297,299],{"key":20,"text":294,"correct":22},"水源",{"key":24,"text":296,"correct":22},"供水设备及管网",{"key":28,"text":298,"correct":22},"雨淋阀组",{"key":31,"text":300,"correct":26},"闭式喷头",{"id":302,"libraryId":5,"type":15,"typeLabel":16,"stem":303,"options":304,"answer":24,"analysis":33},964637,"水喷雾灭火系统是火灾时可向保护对象喷射（ ）灭火或进行防护冷却的灭火系统。",[305,307,309,311],{"key":20,"text":306,"correct":22},"水",{"key":24,"text":308,"correct":26},"水雾",{"key":28,"text":310,"correct":22},"水-泡沫",{"key":31,"text":312,"correct":22},"泡沫-水",{"id":314,"libraryId":5,"type":15,"typeLabel":16,"stem":315,"options":316,"answer":28,"analysis":33},964638,"水喷雾灭火系统按应用方式分不包括（ ）。",[317,319,321,323],{"key":20,"text":318,"correct":22},"泡沫-水喷雾联用系统",{"key":24,"text":320,"correct":22},"固定式水喷雾灭火系",{"key":28,"text":322,"correct":26},"传动管启动水喷雾灭火系统",{"key":31,"text":324,"correct":22},"自动喷水-水喷雾混合配置系统",{"id":326,"libraryId":5,"type":15,"typeLabel":16,"stem":327,"options":328,"answer":31,"analysis":33},964639,"电动启动情况下，当两个或两类探测器同时发出火警信号时，下面哪一项描述不正确？（ ）",[329,331,333,335],{"key":20,"text":330,"correct":22},"水喷雾灭火控制器发出火灾声、光警报信号，通知有火灾发生",{"key":24,"text":332,"correct":22},"有关人员应撤离现场",{"key":28,"text":334,"correct":22},"发出联动指令，关闭风机、防火阀等联动设备",{"key":31,"text":336,"correct":26},"同时发出灭火指令，启动水泵释放灭火剂（水），实施灭火",{"id":338,"libraryId":5,"type":15,"typeLabel":16,"stem":339,"options":340,"answer":28,"analysis":33},964640,"按照传动管启动原理，火灾发生时，以下哪项不正确？（ ）",[341,343,345,347],{"key":20,"text":342,"correct":22},"传动管上的闭式洒水喷水开启",{"key":24,"text":344,"correct":22},"雨淋报警阀开启",{"key":28,"text":346,"correct":26},"经过一段延时后，即发出灭火指令",{"key":31,"text":348,"correct":22},"水雾喷水开始喷水灭火",{"id":350,"libraryId":5,"type":15,"typeLabel":16,"stem":351,"options":352,"answer":24,"analysis":33},964641,"关于水喷雾灭火系统应急机械启动控制方式的说法不正确的是（ ）。",[353,355,357,359],{"key":20,"text":354,"correct":22},"当水喷雾灭火控制器失效时，或在急需紧急启动水喷雾灭火系统时",{"key":24,"text":356,"correct":26},"当消防值班人员再次确认火灾后，应立即通知现场所有人员撤离现场",{"key":28,"text":358,"correct":22},"在确定所有人员撤离现场后，手动关闭消防联动设备并切断非消防电源",{"key":31,"text":360,"correct":22},"在雨淋报警阀所在处所，直接操作对应保护区雨淋报警阀的“手动快开阀”",{"id":362,"libraryId":5,"type":15,"typeLabel":16,"stem":363,"options":364,"answer":24,"analysis":33},964642,"细水雾灭火系统组成部件不包括（ ）。",[365,367,369,371],{"key":20,"text":366,"correct":22},"加压供水设备（泵组或瓶组）",{"key":24,"text":368,"correct":26},"雨淋控制阀组",{"key":28,"text":370,"correct":22},"细水雾喷头",{"key":31,"text":372,"correct":22},"系统管网",{"id":374,"libraryId":5,"type":15,"typeLabel":16,"stem":375,"options":376,"answer":28,"analysis":33},964643,"对细水雾灭火系统的组件描述不正确的是（ ）。",[377,379,381,383],{"key":20,"text":378,"correct":22},"为了防止细水雾喷头堵塞，影响灭火效果，系统还设有过滤器",{"key":24,"text":380,"correct":22},"为了便于系统正常使用、检修维护，系统还设有泄水阀",{"key":28,"text":382,"correct":26},"闭式系统还设有排水阀和试水阀",{"key":31,"text":384,"correct":22},"开式系统还设有泄放试验阀",{"id":386,"libraryId":5,"type":15,"typeLabel":16,"stem":387,"options":388,"answer":24,"analysis":33},964644,"下列对于细水雾灭火系统的分类错误的是（ ）。",[389,391,393,395],{"key":20,"text":390,"correct":22},"按照分配管网中流动介质的压力，可以分为高压系统、中压系统和低压系统；",{"key":24,"text":392,"correct":26},"按照流动介质类型，可以分为水系统和泡沫系统",{"key":28,"text":394,"correct":22},"按照安装方式，可以分为现场安装系统和预安装系统；",{"key":31,"text":396,"correct":22},"按照釆用的细水雾喷头形式，可以分为开式系统和闭式系统；",{"id":398,"libraryId":5,"type":15,"typeLabel":16,"stem":399,"options":400,"answer":28,"analysis":33},964645,"关于细水雾灭火系统的分类不正确的是（ ）。",[401,403,405,407],{"key":20,"text":402,"correct":22},"按照釆用的细水雾喷头形式，可以分为开式系统和闭式系统",{"key":24,"text":404,"correct":22},"按照流动介质类型，可以分为单流体系统和双流体系统",{"key":28,"text":406,"correct":26},"按照系统供水方式可以分为单流体系统和双流体系统",{"key":31,"text":408,"correct":22},"按照安装方式，可以分为现场安装系统和预安装系统",{"id":410,"libraryId":5,"type":15,"typeLabel":16,"stem":411,"options":412,"answer":31,"analysis":33},964646,"泵组式细水雾灭火系统的驱动源不包括（ ）。",[413,415,417,419],{"key":20,"text":414,"correct":22},"柱塞泵",{"key":24,"text":416,"correct":22},"高压离心泵",{"key":28,"text":418,"correct":22},"柴油机泵",{"key":31,"text":420,"correct":26},"汽动泵",{"id":422,"libraryId":5,"type":15,"typeLabel":16,"stem":423,"options":424,"answer":20,"analysis":33},964647,"对瓶组式细水雾灭火系统的描述不正确的是（ ）。",[425,427,429,431],{"key":20,"text":426,"correct":26},"储气瓶组中的储气容器储存常压氮气",{"key":24,"text":428,"correct":22},"储水瓶组中的储水容器储存水",{"key":28,"text":430,"correct":22},"系统启动时释放高压气体驱动水形成细水雾",{"key":31,"text":432,"correct":22},"系统备用状态下，储水容器处于常压状态",{"id":434,"libraryId":5,"type":15,"typeLabel":16,"stem":435,"options":436,"answer":20,"analysis":33},964648,"对开式细水雾灭火系统的工作原理的描述不正确的是（ ）。",[437,439,441,443],{"key":20,"text":438,"correct":26},"当系统的火灾探测器发现火灾后，自动或手动打开雨淋控制阀组",{"key":24,"text":440,"correct":22},"同时发出火灾报警信号给报警控制器",{"key":28,"text":442,"correct":22},"并启动细水雾消防水泵",{"key":31,"text":444,"correct":22},"通过供水管网到达细水雾喷头，细水雾喷头喷水灭火",{"id":446,"libraryId":5,"type":15,"typeLabel":16,"stem":447,"options":448,"answer":31,"analysis":33},964649,"对预作用式细水雾灭火系统准工作状态的描述不正确的是（ ）。",[449,451,453,455],{"key":20,"text":450,"correct":22},"由稳压设施维持预作用阀组入口前管道内充水的压力",{"key":24,"text":452,"correct":22},"预作用报警阀后的管道内平时无水",{"key":28,"text":454,"correct":22},"预作用报警阀后的管道内平时可充以有压气体",{"key":31,"text":456,"correct":26},"预作用报警阀前后管道内压力一致",{"id":458,"libraryId":5,"type":15,"typeLabel":16,"stem":459,"options":460,"answer":31,"analysis":33},964650,"预作用式细水雾灭火系统的工作原理说法不正确的是：（ ）。",[461,463,465,467],{"key":20,"text":462,"correct":22},"发生火灾时，与喷头一起安装在同一保护区的火灾探测器首先发出火灾报警信号",{"key":24,"text":464,"correct":22},"报警控制器确认后，在声光报警的同时即自动启动预作用阀组的驱动装置，",{"key":28,"text":466,"correct":22},"将预作用控制阀打开，开始配水管道排气充水的预作用过程",{"key":31,"text":468,"correct":26},"使系统在开式喷头动作前转换成湿式系统，并能在开式喷头开启后立即喷水",{"id":470,"libraryId":5,"type":15,"typeLabel":16,"stem":471,"options":472,"answer":28,"analysis":33},964651,"以下哪项不是储压型干粉灭火系统的组成部件？（ ）",[473,475,477,479],{"key":20,"text":474,"correct":22},"干粉储罐及其配件",{"key":24,"text":476,"correct":22},"安全泄放装置",{"key":28,"text":478,"correct":26},"干粉控制器",{"key":31,"text":127,"correct":22},{"id":481,"libraryId":5,"type":15,"typeLabel":16,"stem":482,"options":483,"answer":31,"analysis":33},964652,"对储压型干粉灭火系统的工作原理描述不正确的是：（ ）。",[484,486,488,490],{"key":20,"text":485,"correct":22},"当启动机构接收到控制盘的启动信号后动作",{"key":24,"text":487,"correct":22},"通过启动机构开启干粉储存容器的容器阀",{"key":28,"text":489,"correct":22},"容器内的驱动气体驱动干粉灭火剂从容器阀喷出",{"key":31,"text":491,"correct":26},"进而通过选择阀喷向保护空间或者着火对象",{"id":493,"libraryId":5,"type":15,"typeLabel":16,"stem":494,"options":495,"answer":20,"analysis":33},964653,"自动喷水系统系统做水压强度试验，当达到试验压力后应稳压（ ）；且压力降不应大于（ ）。",[496,498,500,502],{"key":20,"text":497,"correct":26},"30min，0.05MPa",{"key":24,"text":499,"correct":22},"24h，0.01MPa",{"key":28,"text":501,"correct":22},"24h，0.05MPa",{"key":31,"text":503,"correct":22},"30min，0.0lMPa",{"id":505,"libraryId":5,"type":15,"typeLabel":16,"stem":506,"options":507,"answer":28,"analysis":33},964654,"柴油机消防泵组的国际标准名称为“工程用柴油机消防泵组”，它以（ ）为动力，驱动消防水泵，输出压力水或空气泡沫混合液进行消防灭火工作。",[508,510,512,514],{"key":20,"text":509,"correct":22},"燃油机",{"key":24,"text":511,"correct":22},"电动机",{"key":28,"text":513,"correct":26},"柴油机",{"key":31,"text":515,"correct":22},"汽油机",{"id":517,"libraryId":5,"type":15,"typeLabel":16,"stem":518,"options":519,"answer":31,"analysis":33},964656,"柴油机消防泵组的组成部分不包括（ ）。",[520,522,524,526],{"key":20,"text":521,"correct":22},"燃油箱",{"key":24,"text":523,"correct":22},"消防泵",{"key":28,"text":525,"correct":22},"蓄电池",{"key":31,"text":527,"correct":26},"公共插座",{"id":529,"libraryId":5,"type":15,"typeLabel":16,"stem":530,"options":531,"answer":31,"analysis":33},964657,"在火灾等紧急情况下，当消防水泵控制柜的控制线路发生故障而供电正常时，为保证及时供水，操作设置在（ ）上的强制机械应急手柄，直接使主回路交流接触器吸合，全压启动消防水泵。",[532,533,535,537],{"key":20,"text":513,"correct":22},{"key":24,"text":534,"correct":22},"柴油机仪表箱动",{"key":28,"text":536,"correct":22},"传动装置",{"key":31,"text":538,"correct":26},"消防水泵控制柜",{"id":540,"libraryId":5,"type":15,"typeLabel":16,"stem":541,"options":542,"answer":28,"analysis":33},964658,"在火灾等紧急情况下，当消防水泵控制柜的控制线路发生故障而供电正常时，为保证及时供水，操作设置在消防水泵控制柜上的强制机械应急手柄，直接使主回路（ ）接触器吸合，全压启动消防水泵。",[543,545,547,549],{"key":20,"text":544,"correct":22},"蓄电",{"key":24,"text":546,"correct":22},"直流",{"key":28,"text":548,"correct":26},"交流",{"key":31,"text":550,"correct":22},"断路",{"id":552,"libraryId":5,"type":15,"typeLabel":16,"stem":553,"options":554,"answer":31,"analysis":33},964659,"关于机械应急启动装置的说法不正确的是（ ）。",[555,557,559,561],{"key":20,"text":556,"correct":22},"机械应急启动装置必须通过消防水泵控制柜的接触器实现",{"key":24,"text":558,"correct":22},"低压机械应急启动装置是在接触器上加装机械装置",{"key":28,"text":560,"correct":22},"高压机械应急启动装置由弹簧蓄能组成",{"key":31,"text":562,"correct":26},"一般消防上常用的为高压机械应急启动装置",{"id":564,"libraryId":5,"type":15,"typeLabel":16,"stem":565,"options":566,"answer":20,"analysis":33},964660,"低压机械应急启动装置是在接触器上加装机械装置，所需的电源是（ ）。",[567,569,571,573],{"key":20,"text":568,"correct":26},"380",{"key":24,"text":570,"correct":22},"1000",{"key":28,"text":572,"correct":22},"6000",{"key":31,"text":574,"correct":22},"10000",{"id":576,"libraryId":5,"type":15,"typeLabel":16,"stem":577,"options":578,"answer":24,"analysis":33},964661,"根据《火灾自动报警系统施工及验收规范》，气体灭火系统应在符合国家现行有关设计规范的条件下按实际安装数量的（ ）的比例抽验其控制功能。",[579,581,583,585],{"key":20,"text":580,"correct":22},"10%-20%",{"key":24,"text":582,"correct":26},"20%-30%",{"key":28,"text":584,"correct":22},"10%-15%",{"key":31,"text":586,"correct":22},"15%-20%",{"id":588,"libraryId":5,"type":15,"typeLabel":16,"stem":589,"options":590,"answer":20,"analysis":33},964662,"低压二氧化碳气体灭火系统在保护铝轧机时应釆用（ ）灭火方式。",[591,593,595,597],{"key":20,"text":592,"correct":26},"全淹没",{"key":24,"text":594,"correct":22},"局部应用",{"key":28,"text":596,"correct":22},"持续喷放",{"key":31,"text":598,"correct":22},"按用量计算喷放时间",{"id":600,"libraryId":5,"type":15,"typeLabel":16,"stem":601,"options":602,"answer":31,"analysis":33},964663,"低压二氧化碳装置储罐压力达到（ ）MPa或低于（ ）MPa时，控制器发出声光报警信号。",[603,605,607,609],{"key":20,"text":604,"correct":22},"2.1，1.9",{"key":24,"text":606,"correct":22},"2.1，1.95",{"key":28,"text":608,"correct":22},"2.2，1.9",{"key":31,"text":610,"correct":26},"2.2，1.8",[612,615,618,621,624,627],{"id":15,"name":613,"category":7,"favorite":614},"领导干部任职前廉政法规知识测试题",92,{"id":616,"name":617,"category":7,"favorite":15},595,"建筑结构与设备",{"id":619,"name":620,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":622,"name":623,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":625,"name":626,"category":7,"favorite":8},534,"BIM工程师",{"id":628,"name":626,"category":7,"favorite":8},535]