[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-701-27":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":642},{"id":5,"name":6,"category":7,"favorite":8},701,"高级技能","建筑工程",0,27,50,2716,[13,35,48,61,73,85,100,113,126,138,150,161,174,186,198,211,223,235,246,258,270,281,293,305,317,329,343,358,371,382,394,409,424,439,453,468,480,488,500,512,524,536,548,560,572,584,596,608,620,632],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":33,"analysis":34},965529,2,"多选题","对于电气火灾监控系统报警测试方法说法正确的是：（ ）。",[19,23,26,29],{"key":20,"text":21,"correct":22},"A","釆用剩余电流发生器模拟产生剩余电流，使探测器达到报警条件，进入报警状态",true,{"key":24,"text":25,"correct":22},"B","釆用可调温式热风机或者其他可控温度的加温设备给探测器的感温元件加温，使探测器达到报警条件，进入报警状态。",{"key":27,"text":28,"correct":22},"C","釆用故障电弧模拟发生装置产生故障电弧，使探测器达到报警条件，进入报警状态。",{"key":30,"text":31,"correct":32},"D","剩余电流发生器通常用于系统生产或验收模拟时测试电气火灾监控探测器灵敏度及报警功能，电流固定，不可调节。",false,"ABC","",{"id":36,"libraryId":5,"type":15,"typeLabel":16,"stem":37,"options":38,"answer":47,"analysis":34},965530,"正压送风机的安装应符合的要求是：（ ）。",[39,41,43,45],{"key":20,"text":40,"correct":22},"风机的设置位置应符合设计要求，设计无要求时，应根据供电条件、风量分配均衡、新风入口不受火、烟烕胁等因素确定",{"key":24,"text":42,"correct":22},"风机的风量、风压应符合设计要求",{"key":27,"text":44,"correct":32},"风机必须釆用轴流风机",{"key":30,"text":46,"correct":22},"风机的供电电源应符合相关规定","ABD",{"id":49,"libraryId":5,"type":15,"typeLabel":16,"stem":50,"options":51,"answer":60,"analysis":34},965531,"防排烟系统中，固定窗的设置和有效面积应符合下列要求：（ ）。",[52,54,56,58],{"key":20,"text":53,"correct":32},"设置在顶层区域的固定窗，其总面积不应小于楼地面面积的5%。",{"key":24,"text":55,"correct":22},"设置在靠外墙且不位于顶层区域的固定窗，单个固定窗的面积不应小于1㎡，且间距不宜大于20m，其下沿距离内地面的高度不宜小于层高的1\u002F2",{"key":27,"text":57,"correct":22},"设置在中庭区域的固定窗，其总面积不应小于中庭楼地面积的5%",{"key":30,"text":59,"correct":22},"固定玻璃窗应按可破拆的玻璃面积计算有效面积","BCD",{"id":62,"libraryId":5,"type":15,"typeLabel":16,"stem":63,"options":64,"answer":33,"analysis":34},965532,"当排烟口设在吊顶内且通过吊顶上部空间进行排烟时，应符合下列规定（ ）。",[65,67,69,71],{"key":20,"text":66,"correct":22},"吊顶应釆用不燃材料，且吊顶内不应有可燃物",{"key":24,"text":68,"correct":22},"封闭式吊顶上设置的烟气流入口的颈部烟气速度不宜大于1.5m\u002Fs",{"key":27,"text":70,"correct":22},"非封闭式吊顶的开孔率不应小于吊顶净面和的25%，且排烟口应均匀布置",{"key":30,"text":72,"correct":32},"非封闭式吊顶的开孔率不应小于吊顶净面积的20%，且排烟口应均匀布置",{"id":74,"libraryId":5,"type":15,"typeLabel":16,"stem":75,"options":76,"answer":60,"analysis":34},965533,"预作用自动喷水灭火系统由（ ）等组成。",[77,79,81,83],{"key":20,"text":78,"correct":32},"开式喷头",{"key":24,"text":80,"correct":22},"供水设施",{"key":27,"text":82,"correct":22},"预作用阀组",{"key":30,"text":84,"correct":22},"充气设备",{"id":86,"libraryId":5,"type":15,"typeLabel":16,"stem":87,"options":88,"answer":99,"analysis":34},965534,"正压送风机的安装应符合下列（ ）要求：",[89,91,93,94,96],{"key":20,"text":90,"correct":22},"风机的设置位置应符合设计要求，设计无要求时，应根据供电条件、风量分配均衡、新风入口不受火、烟烕胁等因素确定。",{"key":24,"text":92,"correct":22},"风机的风量、风压应符合设计要求。",{"key":27,"text":44,"correct":32},{"key":30,"text":95,"correct":22},"风机的供电电源应符合相关规定。",{"key":97,"text":98,"correct":22},"E","控制柜的标志、仪表、指示灯、开关和控制按钮应能正常工作，按钮启、停风机时，仪表及指示灯显示正常。","ABDE",{"id":101,"libraryId":5,"type":15,"typeLabel":16,"stem":102,"options":103,"answer":112,"analysis":34},965535,"柴油发动机的燃油是柴油发动机做机械功的重要工质。关于柴油的说法正确的是（ ）。",[104,106,108,110],{"key":20,"text":105,"correct":22},"轻柴油用于高速柴油机",{"key":24,"text":107,"correct":32},"轻柴油用于中、低速柴油机",{"key":27,"text":109,"correct":32},"重柴油用于高速柴油机",{"key":30,"text":111,"correct":22},"重柴油用于中、低速柴油机","AD",{"id":114,"libraryId":5,"type":15,"typeLabel":16,"stem":115,"options":116,"answer":125,"analysis":34},965536,"关于柴油发电机组的手动启动操作正确的是（ ）选项。",[117,119,121,123],{"key":20,"text":118,"correct":32},"如第一次启动失败，可尝试进行第二次启动。",{"key":24,"text":120,"correct":22},"如第一次启动失败，应待控制屏警报消除、机组恢复正常停车状态后方可进行第二次启动。",{"key":27,"text":122,"correct":32},"启动后，若机器运转声音正常，则说明启动成功。",{"key":30,"text":124,"correct":22},"启动后，若机器运转声音正常、冷却水泵运转指示灯亮及电路仪表指示正常，则说明启动成功。","BD",{"id":127,"libraryId":5,"type":15,"typeLabel":16,"stem":128,"options":129,"answer":47,"analysis":34},965537,"水幕系统处于准工作状态时，由稳压设施维持管道内充水的压力。下面哪一项不属于稳压设施（ ）。",[130,132,134,136],{"key":20,"text":131,"correct":22},"消防水箱",{"key":24,"text":133,"correct":22},"稳压泵",{"key":27,"text":135,"correct":32},"消防转输水泵",{"key":30,"text":137,"correct":22},"气压给水设备",{"id":139,"libraryId":5,"type":15,"typeLabel":16,"stem":140,"options":141,"answer":33,"analysis":34},965538,"仅用水幕系统作为防火分隔时（防火分隔水幕系统），以下说法错误的是（ ）。",[142,144,146,148],{"key":20,"text":143,"correct":22},"应由该报警区域内两只独立的感温火灾探测器的火灾报警信号作为水幕阀组启动的联动触发信号",{"key":24,"text":145,"correct":22},"并应由消防联动控制器联动控制水幕系统相关控制阀组的启动",{"key":27,"text":147,"correct":22},"雨淋报警阀开启，压力开关动作，连锁启动水幕消防泵",{"key":30,"text":149,"correct":32},"应由该报警区域内两只独立的感烟火灾探测器的火灾报警信号作为水幕阀组启动的联动触发信号",{"id":151,"libraryId":5,"type":15,"typeLabel":16,"stem":152,"options":153,"answer":60,"analysis":34},965539,"水幕系统由（ ）等组成。",[154,156,158,160],{"key":20,"text":155,"correct":32},"闭式洒水喷头或水幕喷头",{"key":24,"text":157,"correct":22},"雨淋报警阀组或感温雨淋阀",{"key":27,"text":159,"correct":22},"水流报警装置",{"key":30,"text":80,"correct":22},{"id":162,"libraryId":5,"type":15,"typeLabel":16,"stem":163,"options":164,"answer":173,"analysis":34},965540,"关于水幕系统的说法正确的是（ ）。",[165,167,169,171],{"key":20,"text":166,"correct":32},"水幕系统具备直接灭火的能力，是用于高大空间的防火系统。",{"key":24,"text":168,"correct":22},"水幕系统不具备直接灭火的能力，是用于挡烟阻火和冷却分隔物的防火系统。",{"key":27,"text":170,"correct":22},"按照保护目的不同，可将水幕系统分为防火分隔水幕和防护冷却水幕",{"key":30,"text":172,"correct":32},"按照保护性质不同，可将水幕系统分为防火分隔水幕和防护冷却水幕","BC",{"id":175,"libraryId":5,"type":15,"typeLabel":16,"stem":176,"options":177,"answer":47,"analysis":34},965541,"关于消防设备末端配电装置的描述正确的有（ ）。",[178,180,182,184],{"key":20,"text":179,"correct":22},"常用的消防设备末端配电装置即双电源自动切换装置电器级别为PC级",{"key":24,"text":181,"correct":22},"自动转换开关釆用双列复合式触头、传动机构、微电机预储能以及微电子控制技术",{"key":27,"text":183,"correct":32},"目前，自动转换开关还未实现零飞弧",{"key":30,"text":185,"correct":22},"目前，自动转换开关实现了电源与负载间的隔离",{"id":187,"libraryId":5,"type":15,"typeLabel":16,"stem":188,"options":189,"answer":33,"analysis":34},965542,"消防设备末端配电装置的工作方式包括：（ ）。",[190,192,194,196],{"key":20,"text":191,"correct":22},"自投自复",{"key":24,"text":193,"correct":22},"自投不自复",{"key":27,"text":195,"correct":22},"互为备用",{"key":30,"text":197,"correct":32},"不自投自复",{"id":199,"libraryId":5,"type":15,"typeLabel":16,"stem":200,"options":201,"answer":210,"analysis":34},965543,"消防设备末端配电装置互为备用的工作方式说法正确的是（ ）。",[202,204,206,208],{"key":20,"text":203,"correct":22},"平时双路电源不分主、备用电源供电",{"key":24,"text":205,"correct":32},"当正在使用的电源（A电源）失电时，控制装置使该故障电源（A电源）断路器断开，闭合另一路电源（B电源）断路器，确保临时供电",{"key":27,"text":207,"correct":22},"即故障电源（A电源）恢复正常时，也不必釆取转换恢复（A电源）供电",{"key":30,"text":209,"correct":22},"仅在用电源（B电源）发生失电时，控制装置再将供电电源转换至（A电源）供电","ACD",{"id":212,"libraryId":5,"type":15,"typeLabel":16,"stem":213,"options":214,"answer":210,"analysis":34},965544,"消防设备末端配电装置电网一发电机的工作方式说法正确的是（ ）。",[215,217,219,221],{"key":20,"text":216,"correct":22},"正常时主电源断路器供电",{"key":24,"text":218,"correct":32},"当主电源失电时，控制装置发出指令（无源常开接点），启动发电机发电，主电源断路器立即断开，备用电源断路器闭合",{"key":27,"text":220,"correct":22},"当主电源恢复供电时，控制装置发出指令，停止发电机发电，经延时后使备用电源断路器断开，主电源断路器闭合，恢复主电源断路器供电",{"key":30,"text":222,"correct":22},"转换时间可调整（0-120S）",{"id":224,"libraryId":5,"type":15,"typeLabel":16,"stem":225,"options":226,"answer":210,"analysis":34},965545,"消防设备末端配电装置的功能有（ ）等。",[227,229,231,233],{"key":20,"text":228,"correct":22},"过压保护",{"key":24,"text":230,"correct":32},"欠压保护",{"key":27,"text":232,"correct":22},"断电保护",{"key":30,"text":234,"correct":22},"复位按钮功能",{"id":236,"libraryId":5,"type":15,"typeLabel":16,"stem":237,"options":238,"answer":47,"analysis":34},965546,"消防设备末端配电装置的功能包括（ ）等。",[239,240,242,244],{"key":20,"text":234,"correct":22},{"key":24,"text":241,"correct":22},"手动-自动转换功能",{"key":27,"text":243,"correct":32},"双备功能",{"key":30,"text":245,"correct":22},"电气互锁功能",{"id":247,"libraryId":5,"type":15,"typeLabel":16,"stem":248,"options":249,"answer":210,"analysis":34},965547,"关于消防设备末端配电装置的功能描述正确的是（ ）。",[250,252,254,256],{"key":20,"text":251,"correct":22},"过压保护：当电源电压大于115%Ue（额定工作电压）时，实现转换。",{"key":24,"text":253,"correct":32},"欠压保护：当电源电压小于65%Ue（额定工作电压）时实现转换。",{"key":27,"text":255,"correct":22},"断相保护：当电源任一相断相时，实现转换。",{"key":30,"text":257,"correct":22},"双分功能：设置双分按键，按下双分按键，将主电源、备用电源全部切断。",{"id":259,"libraryId":5,"type":15,"typeLabel":16,"stem":260,"options":261,"answer":47,"analysis":34},965548,"消防设备电源状态监控器的主电源和备用电源转换功能要求为（ ）。",[262,264,266,268],{"key":20,"text":263,"correct":22},"主电源应釆用220V、50Hz电源并设置过流保护措施",{"key":24,"text":265,"correct":22},"电源输入端应设接线端子",{"key":27,"text":267,"correct":32},"当交流电网供电电压变动幅度在额定电压220V的85%-110%范围内，频率偏差不超过标准颗率50Hz的±2%时，监控器应能正常工作",{"key":30,"text":269,"correct":22},"监控器的电源部分应具有主电源和备用电源转换功能，并应有主、备电源工作状态指示",{"id":271,"libraryId":5,"type":15,"typeLabel":16,"stem":272,"options":273,"answer":33,"analysis":34},965549,"消防设备电源状态监控器的主电源和备用电源转换功能正确的有：（ ）。",[274,275,277,279],{"key":20,"text":269,"correct":22},{"key":24,"text":276,"correct":22},"当主电源断电时，能自动转换到备用电源；当主电源恢复时，能自动转换到主电源；",{"key":27,"text":278,"correct":22},"主、备电源的转换不应影响监控器的正常工作",{"key":30,"text":280,"correct":32},"监控器的备用电源在放电至终止电压条件下充电12h所获得的容量应能提供监控器在正常监视状态下至少工作8h",{"id":282,"libraryId":5,"type":15,"typeLabel":16,"stem":283,"options":284,"answer":210,"analysis":34},965550,"消防设备电源状态监控器在下述状况下，应能在100s内发出故障声、光信号：（ ）。",[285,287,289,291],{"key":20,"text":286,"correct":22},"由软件控制实现各顶功能的监控器，当程序不能正常运行时，监控器应有单独的故障指示灯指示主程序故障",{"key":24,"text":288,"correct":32},"监控器自身主电源断电",{"key":27,"text":290,"correct":22},"给监控器自身备用电源充电的充电器与备用电源间连接线的断路、短路",{"key":30,"text":292,"correct":22},"监控器与其分体电源间连接线断路、短路和影响系统功能的接地",{"id":294,"libraryId":5,"type":15,"typeLabel":16,"stem":295,"options":296,"answer":33,"analysis":34},965551,"消防设备电源状态监控器釆用字母（符）-数字显示时，应满足下述要求：（ ）。",[297,299,301,303],{"key":20,"text":298,"correct":22},"应能显示当前中断供电的消防设备总数",{"key":24,"text":300,"correct":22},"按接收到故障的时间先后顺序连续显示各故障部位",{"key":27,"text":302,"correct":22},"当显示区域不足以显示全部故障部位时，应釆用循环方式显示，且应设手动查询按钮",{"key":30,"text":304,"correct":32},"每手动查询一次，可查询全部故障部位及相关信息",{"id":306,"libraryId":5,"type":15,"typeLabel":16,"stem":307,"options":308,"answer":33,"analysis":34},965552,"当釆用公用显示器时，消防设备电源状态监控器的信息显示功能应满足下列要求（ ）。",[309,311,313,315],{"key":20,"text":310,"correct":22},"应优先显示电源中断供电故障信息",{"key":24,"text":312,"correct":22},"其他故障信息的显示不应影响电源中断供电故障信息的显示",{"key":27,"text":314,"correct":22},"电源中断供电故障信息不应与其他信息交替显示",{"key":30,"text":316,"correct":32},"应设循环查询按钮",{"id":318,"libraryId":5,"type":15,"typeLabel":16,"stem":319,"options":320,"answer":125,"analysis":34},965553,"消防设备电源状态监控器有自检、消音、复位功能，关于这些功能说法正确的有（ ）。",[321,323,325,327],{"key":20,"text":322,"correct":32},"监控器应具有自动检查其音响器件、面板所有指示灯和显示器的功能",{"key":24,"text":324,"correct":22},"监控器的自检时间超过lmin或不能自动停止自检时，不应影响非自检部位的正常工作",{"key":27,"text":326,"correct":32},"监控器在故障排除后，故障信号可手动复位",{"key":30,"text":328,"correct":22},"监控器的故障声信号应能手动消除，再有故障信号输入时，应能再启动",{"id":330,"libraryId":5,"type":15,"typeLabel":16,"stem":331,"options":332,"answer":33,"analysis":34},965555,"消防用电设备与适宜备用电源种类一览表中应急发电机组适宜系统使用的是（ ）。",[333,335,337,339,341],{"key":20,"text":334,"correct":22},"自动喷水灭火系统",{"key":24,"text":336,"correct":22},"干粉灭火系统",{"key":27,"text":338,"correct":22},"消防电梯",{"key":30,"text":340,"correct":32},"火灾自动报警系统",{"key":97,"text":342,"correct":32},"消防应急照明和疏散指示系统",{"id":344,"libraryId":5,"type":15,"typeLabel":16,"stem":345,"options":346,"answer":357,"analysis":34},965556,"消防用电设备的配电线路明敷设时（ ）。",[347,349,351,353,355],{"key":20,"text":348,"correct":32},"可不穿管",{"key":24,"text":350,"correct":32},"穿PVC管",{"key":27,"text":352,"correct":32},"穿塑料软管",{"key":30,"text":354,"correct":22},"金属管",{"key":97,"text":356,"correct":22},"封闭式金属线槽","DE",{"id":359,"libraryId":5,"type":15,"typeLabel":16,"stem":360,"options":361,"answer":99,"analysis":34},965557,"（ ）的两个电源或两回路电源，应在最末一级配电箱处设置自动切换装置。",[362,364,366,368,370],{"key":20,"text":363,"correct":22},"消防控制室",{"key":24,"text":365,"correct":22},"消防水泵",{"key":27,"text":367,"correct":32},"空调机",{"key":30,"text":369,"correct":22},"防烟排烟风机",{"key":97,"text":338,"correct":22},{"id":372,"libraryId":5,"type":15,"typeLabel":16,"stem":373,"options":374,"answer":47,"analysis":34},965558,"应急发电机组作为备用电源适宜配接的消防设备系统有（ ）。",[375,376,378,380],{"key":20,"text":338,"correct":22},{"key":24,"text":377,"correct":22},"电动防火窗",{"key":27,"text":379,"correct":32},"火灾报警系统",{"key":30,"text":381,"correct":22},"自动喷水系统",{"id":383,"libraryId":5,"type":15,"typeLabel":16,"stem":384,"options":385,"answer":60,"analysis":34},965559,"水泵启动后工作电流偏大，水泵发热的原因分析（ ）。",[386,388,390,392],{"key":20,"text":387,"correct":32},"空气开关额定工作电流过大",{"key":24,"text":389,"correct":22},"三相不平衡度大于10%",{"key":27,"text":391,"correct":22},"配套电动机功率小",{"key":30,"text":393,"correct":22},"供电电压偏高或偏低",{"id":395,"libraryId":5,"type":15,"typeLabel":16,"stem":396,"options":397,"answer":408,"analysis":34},965560,"机械加压送风系统风机的设置位置在设计无要求时，应根据（ ）等因素决定。",[398,400,402,404,406],{"key":20,"text":399,"correct":32},"安全疏散",{"key":24,"text":401,"correct":22},"供电条件",{"key":27,"text":403,"correct":32},"封闭条件",{"key":30,"text":405,"correct":22},"风量分配均衡",{"key":97,"text":407,"correct":22},"新风入口不受火火、烟威胁","BDE",{"id":410,"libraryId":5,"type":15,"typeLabel":16,"stem":411,"options":412,"answer":423,"analysis":34},965561,"下列关于机械加压送风系统设置要求的说法中不正确的是（ ）。",[413,415,417,419,421],{"key":20,"text":414,"correct":32},"机械加压送风机的进风口宜直通室外",{"key":24,"text":416,"correct":22},"釆用机械加压送风的场所可以设置百叶窗",{"key":27,"text":418,"correct":32},"机械加压送风口的风速不宜大于7m\u002Fs",{"key":30,"text":420,"correct":32},"机械加压送风管道应独立设置在管道井内",{"key":97,"text":422,"correct":22},"未设置在管道井内的加压送风管，其耐火极限不应小于1.0","BE",{"id":425,"libraryId":5,"type":15,"typeLabel":16,"stem":426,"options":427,"answer":438,"analysis":34},965562,"关于加压送风口下列叙述正确的是（ ）。",[428,430,432,434,436],{"key":20,"text":429,"correct":22},"前室、合用前室应每层设一个常闭式加压送风口，并应设手动开启装置。",{"key":24,"text":431,"correct":32},"送风口的风速不宜大于10m\u002Fs",{"key":27,"text":433,"correct":22},"常闭型风口靠感烟（温）信号控制开启，也可手动（或远距离缆绳）开启",{"key":30,"text":435,"correct":22},"送风口不宜设置在被门挡住的部位。",{"key":97,"text":437,"correct":22},"釆用机械加压送风的场所不应设置百叶窗、不宜设置可开启外窗。","ACDE",{"id":440,"libraryId":5,"type":15,"typeLabel":16,"stem":441,"options":442,"answer":33,"analysis":34},965563,"防火阀与排烟防火阀相同之处在于（ ）。",[443,445,447,449,451],{"key":20,"text":444,"correct":22},"能在一定时间内满足耐火稳定性和耐火完整性的要求",{"key":24,"text":446,"correct":22},"能起到阻火隔烟的作用",{"key":27,"text":448,"correct":22},"组成、形状和工作原理相似",{"key":30,"text":450,"correct":32},"安装在相同系统的管道上",{"key":97,"text":452,"correct":32},"动作温度相同",{"id":454,"libraryId":5,"type":15,"typeLabel":16,"stem":455,"options":456,"answer":467,"analysis":34},965564,"火灾状态下排烟系统吸入高温烟雾，当烟温度达到280℃时，应停排烟烟机，以下停排烟机方式正确的是（ ）。",[457,459,461,463,465],{"key":20,"text":458,"correct":22},"排烟防火阀自动关闭，可通过触点开关（串入风机启停回路）直接停排烟风机",{"key":24,"text":460,"correct":32},"消防控制室直接通过切断排烟风机的供电电源停风机",{"key":27,"text":462,"correct":22},"在排烟防火阀附近设置火警联动模块，将防火阀关闭的信号送到消防控制中心，消防中心收到此信号后，再送出指令至排烟风机联动模块停风机",{"key":30,"text":464,"correct":32},"在排烟防火阀附近设置火警联动模块，将防火阀关闭的信号由模块送至排烟风机控制柜停风机",{"key":97,"text":466,"correct":32},"排烟防火阀附近设置火警联动模块直接切断排烟风机电源供电停风","AC",{"id":469,"libraryId":5,"type":15,"typeLabel":16,"stem":470,"options":471,"answer":60,"analysis":34},965565,"机械加压送风系统主要由送风管道、（ ）组成。",[472,474,476,478],{"key":20,"text":473,"correct":32},"可开启外窗",{"key":24,"text":475,"correct":22},"送风口",{"key":27,"text":477,"correct":22},"送风机",{"key":30,"text":479,"correct":22},"吸风口",{"id":481,"libraryId":5,"type":15,"typeLabel":16,"stem":482,"options":483,"answer":60,"analysis":34},965566,"送风系统主要由送风管道、（ ）组成。",[484,485,486,487],{"key":20,"text":473,"correct":32},{"key":24,"text":475,"correct":22},{"key":27,"text":477,"correct":22},{"key":30,"text":479,"correct":22},{"id":489,"libraryId":5,"type":15,"typeLabel":16,"stem":490,"options":491,"answer":112,"analysis":34},965567,"蓄电池充放电测试的方法正确的是：（ ）。",[492,494,496,498],{"key":20,"text":493,"correct":22},"对控制器进行模拟火警、联动等功能测试。控制器仍能工作30min",{"key":24,"text":495,"correct":32},"对蓄电池充电12h后关闭主电开关。使用备用电源供电",{"key":27,"text":497,"correct":32},"控制器连接真实负载的情况下。正常工作12h",{"key":30,"text":499,"correct":22},"关闭控制器主电开关，使用备用电源工作。直至蓄电池放电至终止电压",{"id":501,"libraryId":5,"type":15,"typeLabel":16,"stem":502,"options":503,"answer":210,"analysis":34},965568,"对于蓄电池充放电测试的说法正确的有（ ）。",[504,506,508,510],{"key":20,"text":505,"correct":22},"如控制器蓄电池充放电测试能够满足要求。则说明蓄电池容量正常",{"key":24,"text":507,"correct":32},"如控制器蓄电池充放电测试不能满足要求，则蓄电池需要维修",{"key":27,"text":509,"correct":22},"在进行蓄电池充放电测试过程中，备用电源不能满足正常工作要求时。应能通过声光提示备电欠压",{"key":30,"text":511,"correct":22},"备电欠压声光提示不能消音",{"id":513,"libraryId":5,"type":15,"typeLabel":16,"stem":514,"options":515,"answer":33,"analysis":34},965569,"干粉灭火系统喷头的检查正确的是（ ）。",[516,518,520,522],{"key":20,"text":517,"correct":22},"检查喷嘴安装位置和方向是否正确",{"key":24,"text":519,"correct":22},"检否喷嘴的密封盖是否密封良好",{"key":27,"text":521,"correct":22},"如果系统附有干粉卷车，要检查卷筒转动是否灵活",{"key":30,"text":523,"correct":32},"操作干粉喷枪，检查动作是否灵活",{"id":525,"libraryId":5,"type":15,"typeLabel":16,"stem":526,"options":527,"answer":210,"analysis":34},965570,"干粉灭火系统驱动装置检查内容正确的有（ ）。",[528,530,532,534],{"key":20,"text":529,"correct":22},"检查驱动装置的位置与固定方式是否正常",{"key":24,"text":531,"correct":32},"检查动力气瓶的压力数值是否在设计压力范围内",{"key":27,"text":533,"correct":22},"检查启动气体管路的连接是否正常，是否有移位、损坏、腐蚀现象",{"key":30,"text":535,"correct":22},"检查气瓶阀是否动作灵活",{"id":537,"libraryId":5,"type":15,"typeLabel":16,"stem":538,"options":539,"answer":47,"analysis":34},965571,"干粉灭火系统选择阀的检查内容正确的有：（ ）",[540,542,544,546],{"key":20,"text":541,"correct":22},"检查选择阀及信号反馈装置有无位移、松动",{"key":24,"text":543,"correct":22},"选择阀应有标明对应防护区或保护对象名称的永久标识",{"key":27,"text":545,"correct":32},"如选择阀标识缺失、标注不明，应重新更换",{"key":30,"text":547,"correct":22},"检查选择阀安全销的铅封是否正常",{"id":549,"libraryId":5,"type":15,"typeLabel":16,"stem":550,"options":551,"answer":47,"analysis":34},965572,"干粉灭火系统防护区检查要求正确的是：（ ）",[552,554,556,558],{"key":20,"text":553,"correct":22},"检查防护区的疏散通道是否通畅",{"key":24,"text":555,"correct":22},"检查疏散指示标志和应急照明装置是否正常",{"key":27,"text":557,"correct":32},"检查防护区内和出处的声光报警装置、出口处的安全标志及干粉灭火剂喷放指示门灯是否正常",{"key":30,"text":559,"correct":22},"检查排气装置和泄压装置是否正常",{"id":561,"libraryId":5,"type":15,"typeLabel":16,"stem":562,"options":563,"answer":210,"analysis":34},965573,"对于干粉灭火剂的检查说法正确的是：（ ）",[564,566,568,570],{"key":20,"text":565,"correct":22},"每五年打开干粉储罐的装粉孔，检查干粉质量",{"key":24,"text":567,"correct":32},"干粉质量检查应由维保单位上门检查",{"key":27,"text":569,"correct":22},"干粉质量检查符合规定要求，方可继续使用",{"key":30,"text":571,"correct":22},"若发现干粉灭火剂受潮、变质、结块或者性能检查不合格，应更换新的同类干粉灭火剂",{"id":573,"libraryId":5,"type":15,"typeLabel":16,"stem":574,"options":575,"answer":125,"analysis":34},965574,"柴油发电机组进气系统的检查维护内容包括（ ）。",[576,578,580,582],{"key":20,"text":577,"correct":32},"空滤器到柴油机增压器的连接管路密封应良好，不得有任何缝隙和泄漏现象",{"key":24,"text":579,"correct":22},"进气管内应无杂物，如有杂物应及时清理",{"key":27,"text":581,"correct":32},"柴油机进气管内径应不小于100mm",{"key":30,"text":583,"correct":22},"进气口应加设百叶窗和金属防护网帘，进气口处如有杂物、异物，应及时清理",{"id":585,"libraryId":5,"type":15,"typeLabel":16,"stem":586,"options":587,"answer":210,"analysis":34},965575,"柴油发电机组排气系统的检查维护内容包括（ ）。",[588,590,592,594],{"key":20,"text":589,"correct":22},"散热器与排风口之间是否有弹性减震喇叭形导风槽，如有需连接安装紧固",{"key":24,"text":591,"correct":32},"外接排气管与机组柴油机增压器之间的刚性连接管应无破损且连接紧固",{"key":27,"text":593,"correct":22},"外接排气管应固定牢固，如有松动或产生振动，应及时紧固",{"key":30,"text":595,"correct":22},"排气管内及出口处应无杂物和遮挡，如有应及时进行清理",{"id":597,"libraryId":5,"type":15,"typeLabel":16,"stem":598,"options":599,"answer":210,"analysis":34},965576,"柴油发电机燃油供给系统的检查维护内容正确的有（ ）。",[600,602,604,606],{"key":20,"text":601,"correct":22},"检查燃油箱盖上的通气孔是否畅通，若孔中有污物应清除干净",{"key":24,"text":603,"correct":32},"检查加入的柴油的标号是否符合要求，油量是否充足，油箱油量应在四分之一以上，油路开关应打开",{"key":27,"text":605,"correct":22},"打开减压机构摇转曲轴，检查气缸内喷油的声音",{"key":30,"text":607,"correct":22},"检查油管及接头处有无漏油现象，发现问题及时处理解决",{"id":609,"libraryId":5,"type":15,"typeLabel":16,"stem":610,"options":611,"answer":173,"analysis":34},965577,"剩余电流式电气火灾监控探测器、测温式电气火灾监控探测器、故障电弧探测器运行环境保养要求（ ）。",[612,614,616,618],{"key":20,"text":613,"correct":32},"清除控制器周边的可燃物、杂物",{"key":24,"text":615,"correct":22},"清除探測器与互感器或其他设备之间的遮挡物",{"key":27,"text":617,"correct":22},"检查部件周围是否有漏水、渗水现象",{"key":30,"text":619,"correct":32},"检查控制器的显示是否正常",{"id":621,"libraryId":5,"type":15,"typeLabel":16,"stem":622,"options":623,"answer":210,"analysis":34},965578,"电气火灾监控系统日常保养项目包括（ ）等。",[624,626,628,630],{"key":20,"text":625,"correct":22},"设备外观",{"key":24,"text":627,"correct":32},"接地测试",{"key":27,"text":629,"correct":22},"内部检查及吹扫",{"key":30,"text":631,"correct":22},"报警功能测试",{"id":633,"libraryId":5,"type":15,"typeLabel":16,"stem":634,"options":635,"answer":467,"analysis":34},965579,"电气火灾监控设备的运行环境保养要求包括（ ）。",[636,637,639,641],{"key":20,"text":613,"correct":22},{"key":24,"text":638,"correct":32},"清除探测器与互感器或其他设备之间的遮挡物",{"key":27,"text":640,"correct":22},"检查安装部位是否有漏水、渗水现象",{"key":30,"text":619,"correct":32},[643,647,650,653,656,659],{"id":644,"name":645,"category":7,"favorite":646},1,"领导干部任职前廉政法规知识测试题",92,{"id":648,"name":649,"category":7,"favorite":644},595,"建筑结构与设备",{"id":651,"name":652,"category":7,"favorite":644},715,"招标采购专业知识与法律法规",{"id":654,"name":655,"category":7,"favorite":644},848,"市政方向-通用基础",{"id":657,"name":658,"category":7,"favorite":8},534,"BIM工程师",{"id":660,"name":658,"category":7,"favorite":8},535]