[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-701-23":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":644},{"id":5,"name":6,"category":7,"favorite":8},701,"高级技能","建筑工程",0,23,50,2716,[13,35,48,61,73,88,103,113,126,138,150,163,178,192,204,218,227,241,255,264,273,282,291,306,321,335,350,364,378,390,405,417,432,447,461,474,486,497,509,521,533,541,550,563,575,587,599,608,620,632],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":33,"analysis":34},965322,2,"多选题","下列关于火灾自动报警系统设置，说法正确的是（ ）。",[19,23,27,30],{"key":20,"text":21,"correct":22},"A","从一个防火分区内的任何位置到最邻近的手动火灾报警按钮的直线距离不应大于30m",false,{"key":24,"text":25,"correct":26},"B","区域显示器应设置在出入口等明显和便于操作的部位，当安装在墙上时，其底边距地面高度1.3至1.5m",true,{"key":28,"text":29,"correct":26},"C","消防控制室应设置消防专用电话总机，多线制消防专用电话系统中的每个电话分机应与总机单独连接",{"key":31,"text":32,"correct":22},"D","民用建筑内扬声器应设置在走道和大厅等公共场所，每个扬声器的额定功率不应小于5W。","BC","",{"id":36,"libraryId":5,"type":15,"typeLabel":16,"stem":37,"options":38,"answer":47,"analysis":34},965323,"火灾报警控制器安装在墙上时，要求满足（ ）。",[39,41,43,45],{"key":20,"text":40,"correct":26},"其主显示屏高度宜为1.5m-1.8m",{"key":24,"text":42,"correct":26},"其靠近门轴的侧面距墙不应小于0.5m",{"key":28,"text":44,"correct":22},"正面操作距离不应小于0.5m",{"key":31,"text":46,"correct":26},"正面操作距离不应小于1.2m。","ABD",{"id":49,"libraryId":5,"type":15,"typeLabel":16,"stem":50,"options":51,"answer":60,"analysis":34},965324,"火灾探测报警系统由（ ）组成。",[52,54,56,58],{"key":20,"text":53,"correct":26},"火灾报警控制器",{"key":24,"text":55,"correct":26},"触发器件",{"key":28,"text":57,"correct":26},"火灾警报装置",{"key":31,"text":59,"correct":22},"报警阀","ABC",{"id":62,"libraryId":5,"type":15,"typeLabel":16,"stem":63,"options":64,"answer":60,"analysis":34},965325,"下列述说，属于消防联动控制设备对排烟设施应有控制和显示功能是（ ）。",[65,67,69,71],{"key":20,"text":66,"correct":26},"触发开启相关部位排烟窗、排烟口或排烟阀，并接收其反馈信号",{"key":24,"text":68,"correct":26},"启动相关部位的补风机，并接收其反馈信号",{"key":28,"text":70,"correct":26},"排烟窗、排烟口或排烟阀启动信号触发消防联动控制器，联动控制相关部位排烟风机启动（双速排烟风机切换至高速排烟状态），并接收其反馈信号",{"key":31,"text":72,"correct":22},"联动降落本防火区域的防火卷帘",{"id":74,"libraryId":5,"type":15,"typeLabel":16,"stem":75,"options":76,"answer":87,"analysis":34},965326,"消防控制室内设置的消防设备应包括（ ）或具有相应功能的组合设备。",[77,78,80,82,84],{"key":20,"text":53,"correct":26},{"key":24,"text":79,"correct":26},"消防联动控制器",{"key":28,"text":81,"correct":26},"消防控制室图形显示装置",{"key":31,"text":83,"correct":22},"电气火灾监控系统",{"key":85,"text":86,"correct":26},"E","消防电源监控器设备","ABCE",{"id":89,"libraryId":5,"type":15,"typeLabel":16,"stem":90,"options":91,"answer":102,"analysis":34},965327,"消防控制室设计应符合（ ）等规定。",[92,94,96,98,100],{"key":20,"text":93,"correct":26},"门应向疏散方向开启，且入口处应设明显的标志",{"key":24,"text":95,"correct":26},"送、回风管在其穿墙处应设防火阀",{"key":28,"text":97,"correct":26},"严禁与其无关的电气线路及管路穿过",{"key":31,"text":99,"correct":26},"周围不应布置电磁场干扰较强及其他影响消防控制设备工作的设备用房",{"key":85,"text":101,"correct":22},"应设气体灭火系统","ABCD",{"id":104,"libraryId":5,"type":15,"typeLabel":16,"stem":105,"options":106,"answer":112,"analysis":34},965328,"消防控制室的设置应符合的规定有（ ）。 A.单独建造的消防控制室，其耐火等级不应低于一级 B.附设在建筑内的消防控制室，可设置在建筑物的地下一层或二层，但应釆用耐火极限不低于2.00h的隔墙和不低于1.5h的楼板，与其他部位隔开，并应设置直通室外的安全出口 C.消防控制室送、回风管的穿墙处应设防火阀 D.消防控制室内严禁有与消防设施无关的电气线路及管路穿过",[107,108,109,110,111],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":26},{"key":85,"text":85,"correct":22},"CD",{"id":114,"libraryId":5,"type":15,"typeLabel":16,"stem":115,"options":116,"answer":125,"analysis":34},965329,"下列关于火灾报警控制器在消防控制室内的布置应符合下列（ ）要求。",[117,119,121,123],{"key":20,"text":118,"correct":22},"设备面盘前的操作距离，单列布置时不应小于2m",{"key":24,"text":120,"correct":26},"在值班人员经常工作的一面，设备面盘至墙的距离不应小于3m",{"key":28,"text":122,"correct":26},"设备面盘后的维修距离不宜小于lm",{"key":31,"text":124,"correct":26},"与建筑内其他弱电系统合用的消防控制室内，消防设备应集中设置","BCD",{"id":127,"libraryId":5,"type":15,"typeLabel":16,"stem":128,"options":129,"answer":60,"analysis":34},965330,"消防控制室管理应符合：（ ）。",[130,132,134,136],{"key":20,"text":131,"correct":26},"确保火灾自动报警控制系统处于正常工作状态",{"key":24,"text":133,"correct":26},"确保灭火系统和其他联动控制设备处于正常工作状态",{"key":28,"text":135,"correct":26},"不得将应处于自动状态的系统、设备等设在手动状态",{"key":31,"text":137,"correct":22},"可以将应处于自动状态的系统、设备等设在手动状态",{"id":139,"libraryId":5,"type":15,"typeLabel":16,"stem":140,"options":141,"answer":125,"analysis":34},965331,"常见的火灾自动报警系统的总线设备编码方式有：（ ）。",[142,144,146,148],{"key":20,"text":143,"correct":22},"电动拨码开关",{"key":24,"text":145,"correct":26},"手动拨码开关",{"key":28,"text":147,"correct":26},"电子编码",{"key":31,"text":149,"correct":26},"控制器自动分配",{"id":151,"libraryId":5,"type":15,"typeLabel":16,"stem":152,"options":153,"answer":162,"analysis":34},965332,"在总线设备上使用的手动拨码开关一般分为：（ ）。",[154,156,158,160],{"key":20,"text":155,"correct":26},"二进制",{"key":24,"text":157,"correct":22},"六进制",{"key":28,"text":159,"correct":22},"八进制",{"key":31,"text":161,"correct":26},"十进制","AD",{"id":164,"libraryId":5,"type":15,"typeLabel":16,"stem":165,"options":166,"answer":177,"analysis":34},965333,"消防控制室内设备的布置应符合下列规定（ ）。",[167,169,171,173,175],{"key":20,"text":168,"correct":22},"设备面盘前的操作距离，单列布置时不应小于1.5m；双列布置时不应小于3m；",{"key":24,"text":170,"correct":26},"在值班人员经常工作的一面，设备面盘至墙的距离不应小于3m；",{"key":28,"text":172,"correct":26},"设备面盘后的维修距离不宜小于1m；",{"key":31,"text":174,"correct":26},"设备面盘的排列长度大于4m时，其两端应设置宽度不小于lm的通道；",{"key":85,"text":176,"correct":26},"与建筑其他弱电系统合用的消防控制室内，消防设备应集中设置，并应与其他设备间有明显间","BCDE",{"id":179,"libraryId":5,"type":15,"typeLabel":16,"stem":180,"options":181,"answer":87,"analysis":34},965334,"消防控制设备对室内消火栓系统应有（ ）等控制、显示功能。",[182,184,186,188,190],{"key":20,"text":183,"correct":26},"控制消防水泵的启、停",{"key":24,"text":185,"correct":26},"显示启泵按钮的位置",{"key":28,"text":187,"correct":26},"显示消防水泵的工作、故障状态",{"key":31,"text":189,"correct":22},"显示消火栓栓口的出水压力",{"key":85,"text":191,"correct":26},"防水箱的水位",{"id":193,"libraryId":5,"type":15,"typeLabel":16,"stem":194,"options":195,"answer":60,"analysis":34},965335,"湿式系统和干式系统的联动控制设计，应符合下列（ ）规定。",[196,198,200,202],{"key":20,"text":197,"correct":26},"联动控制方式，湿式报警阀压力开关的动作信号作为触发信号，直接控制启动喷琳消防泵，联动控制不应受消防联动控制器处于自动或手动状态影响；",{"key":24,"text":199,"correct":26},"手动控制方式，将喷淋消防泵控制箱（柜）的启动、停止按钮用专用线路直接连接至设置在消防控制室内的消防联动控制器的手动控制盘，直接手动控制喷淋消防泵的启动、停止；",{"key":28,"text":201,"correct":26},"水流指示器、信号阀、压力开关、喷淋消防泵的启动和停止的动作信号应反馈至火灾报警控制器。",{"key":31,"text":203,"correct":22},"联动控制方式，湿式报警阀压力开关的动作信号作为触发信号，联动控制启动喷琳消防泵，联动控制受消防联动控制器处于自动或手动状态影响",{"id":205,"libraryId":5,"type":15,"typeLabel":16,"stem":206,"options":207,"answer":102,"analysis":34},965336,"下列哪些部位应单独划分探测区域（ ）。",[208,210,212,214,216],{"key":20,"text":209,"correct":26},"敞开或封闭楼梯间、防烟楼梯间；",{"key":24,"text":211,"correct":26},"防烟楼梯间前室、消防电梯前室及合用前室；",{"key":28,"text":213,"correct":26},"电气管道井、通信管道井、电缆隧道；",{"key":31,"text":215,"correct":26},"建筑物闷顶、夹层；",{"key":85,"text":217,"correct":22},"人员不宜进入的场所。",{"id":219,"libraryId":5,"type":15,"typeLabel":16,"stem":220,"options":221,"answer":125,"analysis":34},965337,"雨淋系统的联动控制设计，应符合下列（ ）规定。 A.联动控制方式，由同一报警区域内两只及以上独立的感烟火灾探测器或一只感烟火灾探测器与一只手动火灾报警按钮的报警信号，作为雨淋阀组开启的联动触发信号。应由消防联动控制器控制雨淋阀组的开启； B.手动控制方式，将雨淋消防泵控制箱（柜）的启动和停止按钮、雨琳阀组的启动和停止按钮，用专用线路直接连接至设置在消防控制室内的消防联动控制器的手动控制盘，直接手动控制雨淋消防泵的启动、停止及雨淋阀组的开启； C.水流指示器，压力开关，雨淋阀组、雨淋消防泵的启动和停止的动作信号应反馈至消防联动控制器。 D.联动控制方，由同一报警区域内两只及以上独立的感温火灾探测器或一只感温火灾探测器与一只手动火灾报警按钮的报警信号，作为雨淋阀组开启的联动触发信号。应由消防联动控制器控制雨淋阀组的开启",[222,223,224,225,226],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":26},{"key":85,"text":85,"correct":22},{"id":228,"libraryId":5,"type":15,"typeLabel":16,"stem":229,"options":230,"answer":177,"analysis":34},965338,"消防电梯日常检查的主要内容：（ ）。",[231,233,235,237,239],{"key":20,"text":232,"correct":22},"检查消防电梯载重能力是否符合要求；",{"key":24,"text":234,"correct":26},"检查消防电梯内的消防电话外观是否完好；",{"key":28,"text":236,"correct":26},"检查消防电梯的双电源供电是否正常；",{"key":31,"text":238,"correct":26},"检查消防电梯井的排水泵是否能自动启动；",{"key":85,"text":240,"correct":26},"启动消防电梯迫降模块，观察消防电梯是否降至首层，待门自动打开后，测试消防电梯能否正常工作，并测试首层到顶层所需时间。",{"id":242,"libraryId":5,"type":15,"typeLabel":16,"stem":243,"options":244,"answer":177,"analysis":34},965339,"气体灭火控制器在接收到与首个触发信号不同类别的第二个触发信号后，应发出下列哪些联动控制信号。（ ）",[245,247,249,251,253],{"key":20,"text":246,"correct":22},"切断防护区的非消防电源；",{"key":24,"text":248,"correct":26},"停止通风和空气调节系统及关闭设置在该防护区域的电动防火阀；",{"key":28,"text":250,"correct":26},"联动控制防护区域内开口封闭装置的启动，包括关闭防护区域的门、窗；",{"key":31,"text":252,"correct":26},"关闭防护区域的送（排）风机及送（排风）阀门；",{"key":85,"text":254,"correct":26},"启动气体灭火装置，根据人员安全撤离防护区的需要，气体灭火控制器可设定不大于30s的延迟喷射时间；对于平时无人工作的防护区，可设置为无延迟喷射。",{"id":256,"libraryId":5,"type":15,"typeLabel":16,"stem":257,"options":258,"answer":263,"analysis":34},965340,"（ ）不应作为安全疏散设施。 A.自动扶梯 B.普通电梯 C.室外楼梯 D.直通室外的金属竖向梯",[259,260,261,262],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},"AB",{"id":265,"libraryId":5,"type":15,"typeLabel":16,"stem":266,"options":267,"answer":60,"analysis":34},965341,"消防联动控制器控制受控设备有（ ）等方式。 A.自动总线联动控制 B.总线式手动控制 C.手动直接控制 D.无线遥控器控制",[268,269,270,271,272],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"key":85,"text":85,"correct":22},{"id":274,"libraryId":5,"type":15,"typeLabel":16,"stem":275,"options":276,"answer":47,"analysis":34},965342,"手动直接控制是用专用的线路，对重要的消防设施（ ）进行一对一的控制方式，消防控制室操作人员通过手动直接控制盘手动完成受控设备的联动控制。 A.消防泵 B.喷琳泵 C.消防电梯 D.正压送风机",[277,278,279,280,281],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":26},{"key":85,"text":85,"correct":22},{"id":283,"libraryId":5,"type":15,"typeLabel":16,"stem":284,"options":285,"answer":60,"analysis":34},965343,"下列关于消防水泵不能正常供水的故障原因及排除方法，其中正确的有（ ）。 A.故障原因：水泵进、出水阀门未打开或进水阀未全开；故障排除方法：安全打开进水管阀门 B.故障原因：吸水管内有空气；故障排除方法：打开水泵排气阀门 C.故障原因：底阀打不开；故障排除方法：维修、更换底阀 D.故障原因：电动机旋转方向反向；故障排除方法：电动机电源线的三个接头任意调换两对",[286,287,288,289,290],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"key":85,"text":85,"correct":22},{"id":292,"libraryId":5,"type":15,"typeLabel":16,"stem":293,"options":294,"answer":305,"analysis":34},965344,"火灾报警控制器的安装要求哪些是正确的（ ）。",[295,297,299,301,303],{"key":20,"text":296,"correct":22},"设备面盘前的操作距离单列布置时不应小于1.2m，",{"key":24,"text":298,"correct":26},"设备面盘前的操作距离双列布置时不应小于2m；",{"key":28,"text":300,"correct":26},"设备面盘后的维修距离不宜小于lm；",{"key":31,"text":302,"correct":22},"设备面盘的排列长度大于3m时，其两端应设置宽度不小于1m的通道；",{"key":85,"text":304,"correct":26},"在值班人员经常工作的一面，设备面盘至墙的距离不应小于3m。","BCE",{"id":307,"libraryId":5,"type":15,"typeLabel":16,"stem":308,"options":309,"answer":320,"analysis":34},965345,"报警区域的划分正确的是：（ ）。",[310,312,314,316,318],{"key":20,"text":311,"correct":26},"报警区域应根据防火分区或楼层划分；可将一个防火分区或一个楼层划分为一个报警区域；",{"key":24,"text":313,"correct":26},"将发生火灾时需要同时联动消防设备的相邻几个防火分区或楼层划分为一个报警区域。",{"key":28,"text":315,"correct":22},"防烟楼梯间前室、消防电梯前室、消防电梯与防烟楼梯间合用的前室、走道、坡道划分为一个报警区域。",{"key":31,"text":317,"correct":26},"甲、乙、丙类液体储罐区的报警区域应由一个储罐区组成，每个50000m3及以上的外浮顶储罐应单独划分为一个报警区域。",{"key":85,"text":319,"correct":26},"列车的报警区域应按车厢划分，每节车厢应划分为一个报警区域。","ABDE",{"id":322,"libraryId":5,"type":15,"typeLabel":16,"stem":323,"options":324,"answer":47,"analysis":34},965346,"在火灾自动报警系统中，自动或手动产生火灾报警信号的器件称为触发器件，主要包括（ ）。",[325,327,329,331,333],{"key":20,"text":326,"correct":26},"点型火灾探测器",{"key":24,"text":328,"correct":26},"手动火灾报警按钮",{"key":28,"text":330,"correct":22},"消火栓按钮",{"key":31,"text":332,"correct":26},"线型火灾探测器",{"key":85,"text":334,"correct":22},"输入模块",{"id":336,"libraryId":5,"type":15,"typeLabel":16,"stem":337,"options":338,"answer":349,"analysis":34},965347,"控制中心报警系统是由（ ）等组成的火灾报警系统。",[339,341,343,345,347],{"key":20,"text":340,"correct":26},"消防控制室的消防控制设备",{"key":24,"text":342,"correct":22},"报警阀组",{"key":28,"text":344,"correct":26},"集中报警控制器",{"key":31,"text":346,"correct":26},"区域报警控制器",{"key":85,"text":348,"correct":26},"火灾探测器","ACDE",{"id":351,"libraryId":5,"type":15,"typeLabel":16,"stem":352,"options":353,"answer":87,"analysis":34},965348,"点型火灾探测器有（ ）。",[354,356,358,360,362],{"key":20,"text":355,"correct":26},"离子感烟探测器",{"key":24,"text":357,"correct":26},"光电感烟探测器",{"key":28,"text":359,"correct":26},"点型感温火灾探测器",{"key":31,"text":361,"correct":22},"红外光束感烟火灾探测器",{"key":85,"text":363,"correct":26},"火焰探测器",{"id":365,"libraryId":5,"type":15,"typeLabel":16,"stem":366,"options":367,"answer":320,"analysis":34},965349,"火灾探测器按其响应火灾参数不同，分成（ ）和复合火灾探测器五种基本类型。",[368,370,372,374,376],{"key":20,"text":369,"correct":26},"感温火灾探测器",{"key":24,"text":371,"correct":26},"感烟火灾探测器",{"key":28,"text":373,"correct":22},"红外火焰探测器",{"key":31,"text":375,"correct":26},"可燃气体探测器",{"key":85,"text":377,"correct":26},"感光火灾探测器",{"id":379,"libraryId":5,"type":15,"typeLabel":16,"stem":380,"options":381,"answer":60,"analysis":34},965350,"火灾自动报警系统分为（ ）种形式。",[382,384,386,388],{"key":20,"text":383,"correct":26},"区域报警",{"key":24,"text":385,"correct":26},"集中报警",{"key":28,"text":387,"correct":26},"控制中心报警",{"key":31,"text":389,"correct":22},"通讯中心报警",{"id":391,"libraryId":5,"type":15,"typeLabel":16,"stem":392,"options":393,"answer":404,"analysis":34},965351,"火灾自动报警系统布线检验中，下列（ ）是主要顶检验顶目。",[394,396,398,400,402],{"key":20,"text":395,"correct":26},"强电绝缘导线釆用穿管时，穿管应到位或通过金属软管过渡连接。",{"key":24,"text":397,"correct":22},"弱电绝缘导线釆用穿管时，穿管应到位或通过金属软管过渡连接。",{"key":28,"text":399,"correct":26},"火灾自动报警系统传输线路釆用绝缘导线时，应穿金属管、硬质塑料管、半质塑料菅或封闭线槽保护方式布线。",{"key":31,"text":401,"correct":22},"不同系统、不同电压等级、不同电流类别的线路，不应穿于同一根管内或线槽的同一槽孔。",{"key":85,"text":403,"correct":22},"敷设于多尘或潮湿场所的管路，其管口和管子连接处，应作密封处理。","AC",{"id":406,"libraryId":5,"type":15,"typeLabel":16,"stem":407,"options":408,"answer":87,"analysis":34},965352,"火灾探测报警系统一般由（ ）四部分组成，复杂的系统还包括消防控制设备。",[409,410,412,413,415],{"key":20,"text":55,"correct":26},{"key":24,"text":411,"correct":26},"火灾报警装置",{"key":28,"text":57,"correct":26},{"key":31,"text":414,"correct":22},"通讯装置",{"key":85,"text":416,"correct":26},"电源",{"id":418,"libraryId":5,"type":15,"typeLabel":16,"stem":419,"options":420,"answer":431,"analysis":34},965353,"火灾自动报警系统日常检查主要包括（ ）。",[421,423,425,427,429],{"key":20,"text":422,"correct":26},"外观检查",{"key":24,"text":424,"correct":26},"报警控制器的功能、性能检查",{"key":28,"text":426,"correct":22},"灭火器的检查",{"key":31,"text":428,"correct":22},"疏散通道、安全出口的检查",{"key":85,"text":430,"correct":26},"系统的功能、性能检查","ABE",{"id":433,"libraryId":5,"type":15,"typeLabel":16,"stem":434,"options":435,"answer":446,"analysis":34},965354,"火灾报警后，消防控制设备对防烟、排烟设施应有（ ）等控制、显示功能。",[436,438,440,442,444],{"key":20,"text":437,"correct":26},"停止有关部位的空调送风，关闭电动防火阀，并接收其反馈信号",{"key":24,"text":439,"correct":22},"关闭有关部位的防火门、防火卷帘，并接收再反馈信号，按顺序接通火灾警报装置和火灾应急广播。",{"key":28,"text":441,"correct":26},"启动有关部位的防烟，排烟风机和排烟阀等，并接收其反馈信号",{"key":31,"text":443,"correct":22},"发出控制信号，强制电梯全部停在音层，并接收其反馈信号",{"key":85,"text":445,"correct":26},"控制挡烟垂壁等防烟设施","ACE",{"id":448,"libraryId":5,"type":15,"typeLabel":16,"stem":449,"options":450,"answer":446,"analysis":34},965355,"（ ）场所不宜选用离子感烟探测器。",[451,453,455,457,459],{"key":20,"text":452,"correct":26},"气流速度大于5m\u002Fs",{"key":24,"text":454,"correct":22},"有电气火灾危险的",{"key":28,"text":456,"correct":26},"有大量粉尘、水雾滞留的",{"key":31,"text":458,"correct":22},"高海拔地区",{"key":85,"text":460,"correct":26},"可能产生腐蚀性气体",{"id":462,"libraryId":5,"type":15,"typeLabel":16,"stem":463,"options":464,"answer":473,"analysis":34},965356,"点型火焰探测器的安装要求有（ ）。",[465,467,469,471],{"key":20,"text":466,"correct":26},"探测器与保护目标之间不应有遮挡物",{"key":24,"text":468,"correct":22},"探测器至墙壁、梁边的水平距离，不应小于0.5m",{"key":28,"text":470,"correct":26},"应避免光源直接照射探测器的探测窗口",{"key":31,"text":472,"correct":26},"单波段的火焰探测器不应设置在平时有阳光、白炽灯等光源直接或间接照射的场所","ACD",{"id":475,"libraryId":5,"type":15,"typeLabel":16,"stem":476,"options":477,"answer":473,"analysis":34},965357,"在总线设备上使用的二进制手动拨码开关编码，编码原则正确的是：（ ）。",[478,480,482,484],{"key":20,"text":479,"correct":26},"第一位数：2的0次方",{"key":24,"text":481,"correct":22},"第一位数：2的1次方",{"key":28,"text":483,"correct":26},"最小地址：0",{"key":31,"text":485,"correct":26},"最大地址：255",{"id":487,"libraryId":5,"type":15,"typeLabel":16,"stem":488,"options":489,"answer":60,"analysis":34},965358,"关于总线设备上使用的二进制手动拨码开关编码的描述正确的是：（ ）。",[490,492,494,495],{"key":20,"text":491,"correct":26},"二进制手动拨码开关一般选用8位数",{"key":24,"text":493,"correct":26},"编码范围是0-255",{"key":28,"text":479,"correct":26},{"key":31,"text":496,"correct":22},"第八位数：2的8次方",{"id":498,"libraryId":5,"type":15,"typeLabel":16,"stem":499,"options":500,"answer":47,"analysis":34},965359,"在总线设备上使用的十进制手动拨码开关的说法正确的是：（ ）。",[501,503,505,507],{"key":20,"text":502,"correct":26},"一般选用两个或三个手动拨码开关",{"key":24,"text":504,"correct":26},"最末位开关代表个位，数字范围：0-9；",{"key":28,"text":506,"correct":22},"最末位开关代表百位，数字范围：0-9；",{"key":31,"text":508,"correct":26},"第二位开关代表十位，数字范围：0-9；",{"id":510,"libraryId":5,"type":15,"typeLabel":16,"stem":511,"options":512,"answer":60,"analysis":34},965360,"火灾自动报警系统的总线设备编码的三种编码方式各自的优点描述正确的是：（ ）。",[513,515,517,519],{"key":20,"text":514,"correct":26},"手动拨码开关：操作灵活、直观可见。",{"key":24,"text":516,"correct":26},"电子编码器写码：方便快捷、简单易用。",{"key":28,"text":518,"correct":26},"控制器自动分配电子编码：节省逐一编码的工作量。",{"key":31,"text":520,"correct":22},"电子编码器写码：可小批量统一编码",{"id":522,"libraryId":5,"type":15,"typeLabel":16,"stem":523,"options":524,"answer":263,"analysis":34},965361,"手动拨码开关的弱点有：（ ）。",[525,527,529,531],{"key":20,"text":526,"correct":26},"长时间使用，触点易出现机械故障",{"key":24,"text":528,"correct":26},"易发生拨码不到位致使触点虚连，造成总线设备丢失",{"key":28,"text":530,"correct":22},"总线设备接线故障不易查找",{"key":31,"text":532,"correct":22},"编码无规则",{"id":534,"libraryId":5,"type":15,"typeLabel":16,"stem":535,"options":536,"answer":112,"analysis":34},965362,"控制器自动分配电子编码的不足有：（ ）。",[537,538,539,540],{"key":20,"text":526,"correct":22},{"key":24,"text":528,"correct":22},{"key":28,"text":530,"correct":26},{"key":31,"text":532,"correct":26},{"id":542,"libraryId":5,"type":15,"typeLabel":16,"stem":543,"options":544,"answer":60,"analysis":34},965363,"电子编码器用于对（ ）等总线设备进行读地址、写地址、设置参数等操作。",[545,546,547,548],{"key":20,"text":348,"correct":26},{"key":24,"text":328,"correct":26},{"key":28,"text":330,"correct":26},{"key":31,"text":549,"correct":22},"消防水泵",{"id":551,"libraryId":5,"type":15,"typeLabel":16,"stem":552,"options":553,"answer":562,"analysis":34},965364,"固定式消防给水设备可以釆用由（ ）的消防泵组，也可以釆用由（ ）驱动的消防泵组。",[554,556,558,560],{"key":20,"text":555,"correct":22},"蓄电池驱动",{"key":24,"text":557,"correct":26},"电动机驱动",{"key":28,"text":559,"correct":22},"汽油发动机",{"key":31,"text":561,"correct":26},"柴油发动机","BD",{"id":564,"libraryId":5,"type":15,"typeLabel":16,"stem":565,"options":566,"answer":33,"analysis":34},965365,"当（ ）或（ ）时，消防给水设备经常釆用由柴油机驱动的消防泵组。",[567,569,571,573],{"key":20,"text":568,"correct":22},"主电源不够时",{"key":24,"text":570,"correct":26},"要求双电源",{"key":28,"text":572,"correct":26},"为了进一步提高可靠性",{"key":31,"text":574,"correct":22},"远程无法启动时",{"id":576,"libraryId":5,"type":15,"typeLabel":16,"stem":577,"options":578,"answer":47,"analysis":34},965366,"柴油机消防泵组主要由（ ）等组成。",[579,581,583,585],{"key":20,"text":580,"correct":26},"柴油机消防泵控制柜",{"key":24,"text":582,"correct":26},"消防泵",{"key":28,"text":584,"correct":22},"消防专用电动机",{"key":31,"text":586,"correct":26},"燃油箱",{"id":588,"libraryId":5,"type":15,"typeLabel":16,"stem":589,"options":590,"answer":125,"analysis":34},965367,"下面哪些部件是柴油机消防泵组的组成部分（ ）。",[591,593,595,597],{"key":20,"text":592,"correct":22},"传送装置",{"key":24,"text":594,"correct":26},"仪器仪表",{"key":28,"text":596,"correct":26},"热交换冷却系统",{"key":31,"text":598,"correct":26},"蓄电池",{"id":600,"libraryId":5,"type":15,"typeLabel":16,"stem":601,"options":602,"answer":60,"analysis":34},965368,"柴油机消防泵组的组成部分包括（ ）。",[603,604,605,606],{"key":20,"text":586,"correct":26},{"key":24,"text":582,"correct":26},{"key":28,"text":598,"correct":26},{"key":31,"text":607,"correct":22},"公共插座",{"id":609,"libraryId":5,"type":15,"typeLabel":16,"stem":610,"options":611,"answer":473,"analysis":34},965369,"柴油机消防泵控制柜的基本要求：（ ）。",[612,614,616,618],{"key":20,"text":613,"correct":26},"具有显示柴油机的运行状态和启动成功的信号指示",{"key":24,"text":615,"correct":22},"管网压力检测功能，可根据说明书设置启动压力点",{"key":28,"text":617,"correct":26},"压力记录，故障\u002F报警信息记录",{"key":31,"text":619,"correct":26},"运行、故障\u002F报警反馈输出信号",{"id":621,"libraryId":5,"type":15,"typeLabel":16,"stem":622,"options":623,"answer":263,"analysis":34},965370,"柴油机消防泵组控制方式有：（ ）。",[624,626,628,630],{"key":20,"text":625,"correct":26},"自动启动",{"key":24,"text":627,"correct":26},"手动启动",{"key":28,"text":629,"correct":22},"联动启动",{"key":31,"text":631,"correct":22},"联锁启动",{"id":633,"libraryId":5,"type":15,"typeLabel":16,"stem":634,"options":635,"answer":60,"analysis":34},965371,"柴油机水泵根据（ ）自动启动。",[636,638,640,642],{"key":20,"text":637,"correct":26},"火警信号",{"key":24,"text":639,"correct":26},"电动消防泵启动失败信号",{"key":28,"text":641,"correct":26},"消防水管网的压力低信号",{"key":31,"text":643,"correct":22},"电动消防泵油温高信号",[645,649,652,655,658,661],{"id":646,"name":647,"category":7,"favorite":648},1,"领导干部任职前廉政法规知识测试题",92,{"id":650,"name":651,"category":7,"favorite":646},595,"建筑结构与设备",{"id":653,"name":654,"category":7,"favorite":646},715,"招标采购专业知识与法律法规",{"id":656,"name":657,"category":7,"favorite":646},848,"市政方向-通用基础",{"id":659,"name":660,"category":7,"favorite":8},534,"BIM工程师",{"id":662,"name":660,"category":7,"favorite":8},535]