[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-966907":3},{"question":4,"library":19},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":9},966907,701,3,"判断题","固定消防炮灭火系统联动控制功能验收要求：按设计的联动控制单元进行逐个检查。接通系统电源，使待检联动控制单元的被控设备均处于自动状态，按下对应的联动启动按钮，该单元应能按设计要求自动启动消防泵组，打开阀门等相关设备，直至消防炮喷射灭火剂（或水幕保护系统出水）。该单元设备的动作与信号反馈应符合设计要求。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,{"id":6,"name":20,"category":21,"favorite":22},"高级技能","建筑工程",0]