[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-966661":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":17,"analysis":19},966661,701,3,"判断题","仅启动信号线路故障和电磁阀输入功率不足会造成雨淋自动喷水灭火系统电磁阀不动作。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",false,{"key":16,"text":17,"correct":18},"B","错误",true,"雨淋自动喷水灭火系统电磁阀不动作原因分析：启动信号线路故障，电磁阀输入功率不足，电磁阀损坏。排除方法：检查联动控制启动信号线路，检查电磁阀实际输入功率是否达到额定功率要求，并联设置的每台雨淋阀都应进行检测，联系维修更换电磁阀。",{"id":6,"name":21,"category":22,"favorite":23},"高级技能","建筑工程",0]