[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-966016":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":19},966016,701,3,"判断题","当火灾确认后，火灾自动报警系统应在15s内联动开启相应防烟分区的全部排烟阀、排烟口、排烟风机和补风设备，并应在30s内自动关闭与排烟无关的通风、空调系统。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,"依据《建筑防烟排烟系统技术标准》GB51251-2017，当火灾确认后，火灾自动报警系统应在15s内联动开启相应防烟分区的全部排烟阀、排烟口、排烟风机和补风设施，并应在30s内自动关闭与排烟无关的通风、空调系统。",{"id":6,"name":21,"category":22,"favorite":23},"高级技能","建筑工程",0]