[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965817":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965817,701,2,"多选题","以下哪些符合电气火灾监控系统传感器安装要求？（ ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","传感器与裸带电导体应保证安全距离，金属外壳的传感器应有安全接地",true,{"key":16,"text":17,"correct":14},"B","传感器应独立支承或固定，安装牢固，并应采取防潮、防腐蚀等措施",{"key":19,"text":20,"correct":14},"C","传感器输出回路的连接线，应使用截面积不小于1.0mm2的双绞铜芯导线，并应留有不小于150mm的余量，其端部应有明显标识",{"key":22,"text":23,"correct":24},"D","传感器的安装可以破坏被监控线路的完整性，可以增加线路接点",false,"ABC","电气火灾监控系统传感器安装要求：传感器与裸带电导体应保证安全距离，金属外壳的传感器应有安全接地；传感器应独立支承或固定，安装牢固，并应采取防潮、防腐蚀等措施；传感器输出回路的连接线，应使用截面积不小于1.0mm2的双绞铜芯导线，并应留有不小于150mm的余量，其端部应有明显标识；传感器的安装不应破坏被监控线路的完整性，不应增加线路接点。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]