[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965806":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965806,701,2,"多选题","下面符合固定消防炮灭火系统联动控制功能验收要求的是：（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","对设计的联动控制单元进行抽查",false,{"key":16,"text":17,"correct":18},"B","接通系统电源，使待检联动控制单元的被控设备均处于自动状态，按下对应的联动启动按钮，该单元应能按设计要求自动启动消防泵组",true,{"key":20,"text":21,"correct":18},"C","打开阀门等相关设备，直至消防炮喷射灭火剂（或水幕保护系统出水）",{"key":23,"text":24,"correct":18},"D","该单元设备的动作与信号反馈应符合设计要求","BCD","固定消防炮灭火系统联动控制功能验收要求：按设计的联动控制单元进行逐个检查。接通系统电源，使待检联动控制单元的被控设备均处于自动状态，按下对应的联动启动按钮，该单元应能按设计要求自动启动消防泵组，打开阀门等相关设备，直至消防炮喷射灭火剂（或水幕保护系统出水）。该单元设备的动作与信号反馈应符合设计要求。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]