[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965800":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965800,701,2,"多选题","灭火剂储存装置的安装要求包括：（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","储存装置的安装位置应符合设计文件的要求",true,{"key":16,"text":17,"correct":18},"B","灭火剂储存装置安装后，泄压装置的泄压方向应朝向操作面",false,{"key":20,"text":21,"correct":14},"C","低压二氧化碳灭火系统的安全阀应通过专用的泄压管接到室外",{"key":23,"text":24,"correct":14},"D","储存装置上压力计、液位计、称重显示装置的安装位置应便于人员观察和操作","ACD","灭火剂储存装置的安装要求： （1）储存装置的安装位置应符合设计文件的要求。 （2）灭火剂储存装置安装后，泄压装置的泄压方向不应朝向操作面。低压二氧化破灭火系统的安全阀应通过专用的泄压管接到室外。 （3）储存装置上压力计、液位计、称重显示装置的安装位置应便于人员观察和操作。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]