[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965767":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965767,701,2,"多选题","气体灭火系统手动启动\u002F停止按钮、手动\u002F自动转换装置的安装符合要求的有：（ ）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","放气指示灯一般安装在防护区疏散门外的上方，便于观察的地方",true,{"key":16,"text":17,"correct":14},"B","放气指示灯应安装牢固",{"key":19,"text":20,"correct":21},"C","放气指示灯连接导线应留有不小于200mm的余量，且在其端部应有明显标志",false,{"key":23,"text":24,"correct":14},"D","当气体灭火系统手动启动\u002F停止按钮、手动\u002F自动转换装置安装在墙上时，其底边距地（楼）面高度宜为1.3-1.5m","ABD","气体灭火系统手动启动\u002F停止按钮、手动\u002F自动转换装置的安装要求： （1）手动启动\u002F停止按钮、手动\u002F自动转换装置应安装在明显和便于操作的部位。当安装在墙上时，其底边距地（楼）面高度宜为1.3-1.5m （2）放气指示灯，放气指示灯一般安装在防护区疏散门外的上方，便于观察的地方。要求：安装牢固；连接导线应留有不小于150mm的余量，且在其端部应有明显标志。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]