[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965755":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},965755,701,2,"多选题","消防水泵自动巡检时，巡检功能应符合下列规定（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","巡检周期不宜大于7d，且应能按需要任意设定；",true,{"key":16,"text":17,"correct":18},"B","以低频交流电源逐台驱动消防水泵，使每台消防水泵低速转动的时间不应少于3min；",false,{"key":20,"text":21,"correct":18},"C","对消防水泵控制柜一次回路中的主要器件宜有巡检功能，并应检查器件的动作状态；",{"key":23,"text":24,"correct":14},"D","当有消防信号时应立即退出巡检，进入消防运行状态；",{"key":26,"text":27,"correct":14},"E","发现故障时应有声、光报警，并应有记录和储存功能；自动巡检时应设置电源自动切换功能的检查。","ADE","消防水泵自动巡检时，以低频交流电源逐台驱动消防水泵，使每台消防水泵低速转动的时间不应少于2min；对消防水泵控制柜一次回路中的主要低压器件宜有巡检功能，并应检查器件的动作状态。",{"id":6,"name":31,"category":32,"favorite":33},"高级技能","建筑工程",0]