[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965743":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965743,701,2,"多选题","吸气式感烟火灾探测器的操作可靠性取决于烟雾传感器的功能可靠性和系统的持续空气供给，若出现（ ）等现象，导致探测器吸气流量大于正常吸气流量的150%或小于正常吸气流量的50%时，探测器应在100s内发出故障信号。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","风机发生故障",true,{"key":16,"text":17,"correct":14},"B","探测器吸气管路发生破漏",{"key":19,"text":20,"correct":14},"C","探测器吸气管路发生堵塞",{"key":22,"text":23,"correct":24},"D","在任一采样孔获取的火灾烟雾参数符合报警条件",false,"ABC","吸气式感烟火灾探测器的操作可靠性取决于烟雾传感器的功能可靠性和系统的持续空气供给，若风机发生故障、探测器吸气管路发生破漏或堵塞等现象，导致探测器吸气流量大于正常吸气流量的150%或小于正常吸气流量的50%时，探测器应在100s内发出故障信号。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]