[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965739":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965739,701,2,"多选题","吸气式感烟火灾探测器灵敏度要求包括：（ ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","天棚高度大于16m的场所，探测器应设为最高灵敏度",true,{"key":16,"text":17,"correct":14},"B","天棚高度大于16m的场所，保证至少有两个采样孔低于16m",{"key":19,"text":20,"correct":14},"C","非高灵敏度的吸气式感烟火灾探测器不宜安装在天棚高度大于16m的场所",{"key":22,"text":23,"correct":24},"D","探测器的探测视角内不应存在遮挡物",false,"ABC","吸气式感烟火灾探测器灵敏度要求：天棚高度大于16m的场所，探测器应设为最髙灵敏度，并保证至少有两个采样孔低于16m；非高灵敏度的吸气式感烟火灾探测器不宜安装在天棚高度大于16m的场所",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]