[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965719":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965719,701,2,"多选题","可燃气体探测报警系统出现某一回路可燃气体探测器全部掉线故障，请问如何维修？（ ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","检查该回路供电\u002F通信连接线是否断开，连接好该回路供电\u002F通信连接线路",true,{"key":16,"text":17,"correct":14},"B","用万用表检查探测器回路供电\u002F通信线路是否存在短路情况，排查短路故障",{"key":19,"text":20,"correct":14},"C","利用兆欧表（揺表）检测该回路供电\u002F通信线路与大地之间的接地电阻。",{"key":22,"text":23,"correct":24},"D","阻值大于产品说明书中的绝缘要求则为接地故障，利用分段法排查回路线路接地点并修复接地故障",false,"ABC","某一回路可燃气体探测器全部掉线故障原因： （1）探测器供电线路短路或者断开 （2）探测器通信线路短路或者断开 （3）该回路出现接地故障 维修方法： （1）检查该回路供电\u002F通信连接线是否断开，连接好该回路供电\u002F通信连接线路 （2）用万用表检查探测器回路供电\u002F通信线路是否存在短路情况，排查短路故障 （3）利用兆欧表（揺表）检测该回路供电\u002F通信线路与大地之间的接地电阻。阻值小于产品说明书中的绝缘要求则为接地故障，利用分段法排查回路线路接地点并修复接地故障",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]