[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965668":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},965668,701,2,"多选题","下列关于灭火器配置场所计算单元的划分说法正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","对于不相邻的灭火器配置场所，应分别作为一个计算单元进行灭火器的配置设计计算",true,{"key":16,"text":17,"correct":14},"B","灭火器配置场所的危险等级和火灾种类均相同的相邻场所，可将一个楼层或一个防火分区作为一个计算单元",{"key":19,"text":20,"correct":21},"C","同一计算单元可以跨越防火分区和楼层",false,{"key":23,"text":24,"correct":14},"D","灭火器配置场所的危险等级或火灾种类不相同的场所，应分别作为一个计算单元",{"key":26,"text":27,"correct":21},"E","—个计算单元只能含有一个灭火器配置场所","ABD","（1）对危险等级和火灾种类均相同的若干相连通的灭火器配置场所。可将一个楼层或一个防火分区作为一个计算单元。但不得跨越楼层或防火分区； （2）对危险等级或火灾种类不相同的灭火器配置场所。应分别作为一个计算单元； （3）普通住宅应以户为计算单元。",{"id":6,"name":31,"category":32,"favorite":33},"高级技能","建筑工程",0]