[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965652":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965652,701,2,"多选题","预作用自动喷水灭火系统传动管喷头堵塞的原因是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","消防用水水质存在问题，如有杂物等",true,{"key":16,"text":17,"correct":14},"B","管道过滤器不能正常工作",{"key":19,"text":20,"correct":21},"C","阀瓶损坏或胶垫脱落",false,{"key":23,"text":24,"correct":21},"D","末端试水装置阀门未关或关闭不严","AB","故障现象：预作用自动喷水灭火系统传动管喷头堵塞原因分析：消防用水水质存在问題，如有杂物等，管道过滤器不能正常工作。排除方法：对水质进行检测，清理不干净、影响系统正常使用的消防用水，检查管道滤器，消除滤网上的杂质或者更换过滤器。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]