[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965647":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965647,701,2,"多选题","关于预作用自动喷水灭火系统预作用装置故障描述正确的有（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","气体平稳补偿功能失效会导致预作用装置误报警",true,{"key":16,"text":17,"correct":14},"B","管道内有大量空气会导致预作用装置间歇报警",{"key":19,"text":20,"correct":14},"C","水中杂质导致阀瓣关闭不严会导致预作用装置一直报警",{"key":22,"text":23,"correct":24},"D","末端试水装置阀门未关或关闭不严会导致预作用装置间歇报警",false,"ABC","气体平稳补偿功能失效会导致预作用自动喷水灭火系统预作用装置误报警。管道内有大量空气会导致预作用自动喷水灭火系统预作用装置间歇报警，预作用自动喷水灭火系统的预作用装置一直报警原因分析：水中杂质导致阀瓣关闭不严，末端试水装置阀门未关或关闭不严，阀瓣损坏或胶垫脱落。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]