[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965624":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":24,"analysis":25},965624,701,2,"多选题","预作用自动喷水灭火系统出现预作用装置一直报警原因是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","水中杂质导致阀瓣关闭不严",true,{"key":16,"text":17,"correct":14},"B","末端试水装置阀门未关或关闭不严",{"key":19,"text":20,"correct":14},"C","阀瓣损坏或胶垫脱落",{"key":22,"text":17,"correct":23},"D",false,"ABC","故障现象：预作用自动喷水灭火系统的预作用装置一直报警原因分析：水中杂质导致阀瓣关闭不严，末端试水装置阀门未关或关闭不严，阀瓣损坏或胶垫脱落。排除方法：用水冲洗或清理杂质，关闭末端试水装置阀门，检査胶垫或阀瓣。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]