[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965621":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965621,701,2,"多选题","维保时发现某单位雨淋自动喷水灭火系统雨淋报警阀不能进入伺应状态，需如何排除此问题（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","修复或者更换复位装置",true,{"key":16,"text":17,"correct":14},"B","开启隔膜室控制阀、复位球阀",{"key":19,"text":20,"correct":14},"C","将供水控制阀关闭，拆下过滤器的滤网，用清水冲洗干净后，重新安装到位",{"key":22,"text":23,"correct":24},"D","开启放水控制阀，排除系统侧管道内的余水",false,"ABC","雨淋自动喷水灭火系统雨淋报警阀不能进入伺应状态原因分析：复位装置存在问题，未按照安装调试说明书将报警阀组调试到伺应状态（隔膜室控制阀、复位球阀未关闭）消防用水水质存在同题，杂质堵塞了隔膜室管道上的过滤器。排除方法：修复或者更换复位装置，按照安装调试说明书将报警阀组调试到伺应状态（开启隔膜室控制阀、复位球阀）将供水控制阀关闭，拆下过滤器的滤网，用淸水冲洗干净后，重新安装到位。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]