[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965620":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965620,701,2,"多选题","如何排除预作用自动喷水灭火系统出现压力表读数不在正常范围的故障（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","完全开启报警阀前的供水控制阀",true,{"key":16,"text":17,"correct":14},"B","拆卸压力表及其管路，疏通压力表管路",{"key":19,"text":20,"correct":21},"C","关闭末端试水装置阀门",false,{"key":23,"text":24,"correct":14},"D","完全开启压力表管路控制阀","ABD","故障现象：预作用自动喷水灭火系统压力表读数不在正常范围排除方法：完全开启报警阀前的供水控制阀，拆卸压力表及其管路，疏通压力管路，按照湿式报警阀组渗漏的原因进行检查、分析，査找预作用报警装置的报警阀体的漏水部位，修复或者更换组件，完全开启压力表管路控制阀。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]