[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965564":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},965564,701,2,"多选题","火灾状态下排烟系统吸入高温烟雾，当烟温度达到280℃时，应停排烟烟机，以下停排烟机方式正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","排烟防火阀自动关闭，可通过触点开关（串入风机启停回路）直接停排烟风机",true,{"key":16,"text":17,"correct":18},"B","消防控制室直接通过切断排烟风机的供电电源停风机",false,{"key":20,"text":21,"correct":14},"C","在排烟防火阀附近设置火警联动模块，将防火阀关闭的信号送到消防控制中心，消防中心收到此信号后，再送出指令至排烟风机联动模块停风机",{"key":23,"text":24,"correct":18},"D","在排烟防火阀附近设置火警联动模块，将防火阀关闭的信号由模块送至排烟风机控制柜停风机",{"key":26,"text":27,"correct":18},"E","排烟防火阀附近设置火警联动模块直接切断排烟风机电源供电停风","AC","停止排烟机方式正确的是排烟防火阀自动关闭，可通过触点开关（串入风机启停回路）直接停排烟风机；在排烟防火阀附近设置火警联动模块，将防火阀关闭的信号送到消防控制中心，消防中心收到此信号后，再送出指令至排烟风机联动模块停风机。",{"id":6,"name":31,"category":32,"favorite":33},"高级技能","建筑工程",0]