[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965532":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965532,701,2,"多选题","当排烟口设在吊顶内且通过吊顶上部空间进行排烟时，应符合下列规定（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","吊顶应釆用不燃材料，且吊顶内不应有可燃物",true,{"key":16,"text":17,"correct":14},"B","封闭式吊顶上设置的烟气流入口的颈部烟气速度不宜大于1.5m\u002Fs",{"key":19,"text":20,"correct":14},"C","非封闭式吊顶的开孔率不应小于吊顶净面和的25%，且排烟口应均匀布置",{"key":22,"text":23,"correct":24},"D","非封闭式吊顶的开孔率不应小于吊顶净面积的20%，且排烟口应均匀布置",false,"ABC","依据《建筑防烟排烟系统技术标准》GB51251-2017，当排烟口设在吊顶内且通过吊顶上部空间进行排烟时，应符合下列规定： （1）吊顶应釆用不燃材料，且吊顶内不应有可燃物。 （2）封闭式吊顶上设置的烟气流入口的颈部烟气速度不宜大于1.5m\u002Fs。 （3）非封闭式吊顶的开孔率不应小于吊顶净面积的25%，且孔洞应均匀布置。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]