[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965528":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965528,701,2,"多选题","电气火灾监控系统的报警功能描述正确的有（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","当被保护线路剩余电流达到报警设定值时，剩余电流式电气火灾监控探测器应40s内发出报警信号。",false,{"key":16,"text":17,"correct":14},"B","当被监视部位温度达到报警设定值时，测温式电气火灾监控探测器应在30s内发出报警信号。",{"key":19,"text":20,"correct":21},"C","当被探测线路在1s内发生14个及以上半周期的故障电弧时，故障电弧探测器应在30s内发出报警信号。",true,{"key":23,"text":24,"correct":21},"D","电气火灾监控设备应能接收来自探测器的报警信号，并在10s内发出声、光报警信号，指示报警部位，显示报警时间。","CD","电气火灾监控系统的报警功能：当被保护线路剩余电流达到报警设定值时，剩余电流式电气火灾监控探测器应30s内发出报警信号。当被监视部位温度达到报警设定值时，测温式电气火灾监控探测器应在40s内发出报警信号。当被探测线路在1s内发生14个及以上半周期的故障电弧时，故障电弧探测器应在30s内发出报警信号。电气火灾监控设备应能接收来自探测器的报警信号，并在10s内发出声、光报警信号，指示报警部位，显示报警时间。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]