[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965501":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965501,701,2,"多选题","当自动控制的水幕系统用于防火卷帘的保护时（防护冷却水幕系统），应由（ ）组成“与”逻辑作为水幕阀组启动的联动触发信号，并应由消防联动控制器联动控制水幕系统相关控制阀组的启动，雨淋报警阀开启，压力开关动作，连锁启动水幕消防泵。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","防火卷帘下落到楼板面的动作信号与本报警区域内任一火灾探测器的报警信号",true,{"key":16,"text":17,"correct":18},"B","防火卷帘下落到1.8m的动作信号与本报警区域内任一火灾探测器的报警信",false,{"key":20,"text":21,"correct":14},"C","防火卷帘下落到楼板面的动作信号与本报警区域内任一手动火灾报警按钮的报警信号",{"key":23,"text":24,"correct":18},"D","防火卷帘下落到1.8m的动作信号与本报警区域内不同火灾探测器的报警信号","AC","当自动控制的水幕系统用于防火卷帘的保护时（防护冷却水幕系统），应由防火卷帘下落到楼板面的动作信号与本报警区域内任一火灾探测器或手动火灾报警按钮的报警信号组成“与”逻辑作为水幕阀组启动的联动触发信号，并应由消防联动控制器联动控制水幕系统相关控制阀组的启动，雨淋报警阀开启，压力开关动作，连锁启动水幕消防泵。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]