[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965492":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965492,701,2,"多选题","（ ）时，用应急机械启动控制方式启动水喷雾灭火系统。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","水喷雾灭火控制器失效",true,{"key":16,"text":17,"correct":14},"B","急需紧急启动水喷雾灭火系统",{"key":19,"text":20,"correct":21},"C","消防值班人员确认有火灾时",false,{"key":23,"text":24,"correct":21},"D","经过一段延时后","AB","当水喷雾灭火控制器失效时，或在急需紧急启动水喷雾灭火系统时，当消防值班人员判断为火灾时，应立即通知现场所有人员撤离现场，在确定所有人员撤离现场后，手动关闭消防联动设备并切断非消防电源。在雨淋报警阀所在处所，直接操作对应保护区雨淋报警阀的“手动快开阀”，使雨淋报警阀开启，同时启动消防水泵，即刻实施灭火。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]