[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965456":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},965456,701,2,"多选题","湿式报警阀组安装应符合下列（ ）规定。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","报警阀组的安装应在供水管网试压、冲洗合格前进行",false,{"key":16,"text":17,"correct":18},"B","安装时应先安装水源控制阀、报警阀，然后进行报警阀辅助管道的连接，水源控制阀、报警阀与配水干管的连接，应使水流方向一致。",true,{"key":20,"text":21,"correct":18},"C","报警阀组安装的位置应符合设计要求；当设计无要求时，报警阀组应安装在便于操作的明显位置，距室内地面高度宜为1.2m；两侧与墙的距离不应小于0.5m；正面与墙的距离不应小于1.2m；报警阀组凸出部位之间的距离不应小于0.5m。",{"key":23,"text":24,"correct":18},"D","安装报警阀组的室内地面应有排水设施。","BCD","报警阀组的安装应在供水管网试压、冲洗合格后进行。",{"id":6,"name":28,"category":29,"favorite":30},"高级技能","建筑工程",0]