[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965445":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},965445,701,2,"多选题","下列关于预作用系统功能测试检测要求正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","报警阀组动作后，测试水水力警铃声强，不得低于60dB",false,{"key":16,"text":17,"correct":14},"B","开启末端试水装置，火灾报警控制器确认火灾lmin后，其出水压力不低于0.05MPa",{"key":19,"text":20,"correct":21},"C","模拟火灾探测报警，火灾报警控制器确认火灾后，自动启动预作用装置（雨淋报警阀）、排气阀入口电动阀以及消防水泵；水流指示器、压力开关动作",true,{"key":23,"text":24,"correct":21},"D","消防控制设备准确显示电磁阀、电动阀、水流指示器以及消防水泵动作信号，反馈信号准确",{"key":26,"text":27,"correct":14},"E","检查报警阀组外观标志，标识清晰、内容详实，符合产品生产技术标准要求，并注明系统名称和保护区域，压力表显示符合设定值","CD","预作用系统功能测试检测要求：报警阀组动作后，测试水水力警铃声强，不得低于70dB；开启末端试水装置，火灾报警控制器确认火灾2min后，其出水压力不低于0.05MPa。检查报警阀组外观等为共性检查，不属于功能检测。",{"id":6,"name":31,"category":32,"favorite":33},"高级技能","建筑工程",0]