[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965311":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},965311,701,2,"多选题","故障电弧探测器的设置位置及安装应符合下列要求：（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","应以设置在低压配电系统首端为基本原则，宜设置在第一级配电箱（柜）的出线端，在供电线路泄露电流大于500mA时，宜在下一级配电柜（箱）设置；",false,{"key":16,"text":17,"correct":14},"B","应设置在电缆接头、端子、重点发热部件等部位；",{"key":19,"text":20,"correct":14},"C","保护对象为1000V及以下的配电线路，应釆用接触式布置；",{"key":22,"text":23,"correct":24},"D","探测器的额定工作电流应与被探测线路的工作电流相匹配，其保护线路的长度不宜大于100m；",true,{"key":26,"text":27,"correct":24},"E","探测器应可靠固定，防止松动或位移。","DE","在设置和安装故障电弧探测器时，探测器的额定工作电流应与被探测线路的工作电流相匹配，其保护线路的长度不宜大于100m；探测器应可靠固定，防止松动或位移。",{"id":6,"name":31,"category":32,"favorite":33},"高级技能","建筑工程",0]