[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965304":3},{"question":4,"library":25},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":23,"analysis":24},965304,701,2,"多选题","不宜选用点型离子感烟探测器的场所是：（ ）。 A.气流速度大于5m\u002Fs B.有电气火灾危险的 C.有大量粉尘、水雾滞留的 D.高海拔地区",[11,14,17,19,21],{"key":12,"text":12,"correct":13},"A",true,{"key":15,"text":15,"correct":16},"B",false,{"key":18,"text":18,"correct":13},"C",{"key":20,"text":20,"correct":16},"D",{"key":22,"text":22,"correct":16},"E","AC","依据《火灾自动报警系统设计规范》GB50116-2013，符合下列条件之一的场所，不宜选择点型离子感烟火灾探测器： （1）相对湿度度经常大于95%。 （2）气流速度大于5m\u002Fs。 （3）有大量粉尘、水雾滞留。 （4）可能产生腐蚀性气体。 （5）在正常情况下有烟滞留。 （6）产生醇类、醚类、酮类等有机物质。本题答案为AC。",{"id":6,"name":26,"category":27,"favorite":28},"高级技能","建筑工程",0]