[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965208":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},965208,701,1,"单选题","不符合剩余流式电气火灾监控探测器监控报警功能要求的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","探测器监测区域的剩余电流达到报警设定值时，探测器的报警确认灯应在30s内点亮并保持；",false,{"key":16,"text":17,"correct":14},"B","监控设备应发出监控报警声、光信号，并记录报警时间；",{"key":19,"text":20,"correct":14},"C","监控设备应显示发出报警信号部件的地址注释信息。",{"key":22,"text":23,"correct":24},"D","探测器监测区域的温度达到报警设定值时，探测器的报警确认灯应在40s内点亮并保持；",true,"剩余流式电气火灾监控探测器监控报警功能要求：探测器监测区域的剩余电流达到报警设定值时，探测器的报警确认灯应在30s内点亮并保持；监控设备应发出监控报警声 、光信号，并记录报警时间；监控设备应显示发出报警信号部件的地址注释信息.",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]