[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965189":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},965189,701,1,"单选题","对于灭火剂输送管道水压强度试验的说法不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","对高压二氧化碳灭火系统，试验压力应取15.0MPa",false,{"key":16,"text":17,"correct":14},"B","对低压二氧化碳灭火系统，试验压力应取4.0MPa",{"key":19,"text":20,"correct":21},"C","进行水压强度试验时，以不大于0.5MPa\u002Fs的升压速率缓慢升压至试验压力。保压l0min，检查管道各处无渗漏，无变形为合格",true,{"key":23,"text":24,"correct":14},"D","当水压强度试验条件不具备时，可采用气压强度试验代替。","对高压二氧化碳灭火系统，应取15.0MPa；对低压二氧化碳灭火系统，应取4.0MPa。进行水压强度试验时，以不大于0.5MPa\u002Fs的升压速率缓慢升压至试验压力。保压5min，检查管道各处无渗漏，无变形为合格。当水压强度试验条件不具备时，可采用气压强度试验代替。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]