[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965177":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},965177,701,1,"单选题","消防给水系统管网的正常泄漏量应根据管道材质、接口形式等确定，当没有管网泄漏量数据时，稳压泵的设计流量宜按消防给水设计流量的1%-3%计，且不宜小于（ ）L\u002Fs。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1",true,{"key":16,"text":17,"correct":18},"B","2",false,{"key":20,"text":21,"correct":18},"C","3",{"key":23,"text":24,"correct":18},"D","4","在GB50974-2014消防给水及消火栓系统技术规范中：5.3.2-1稳压泵的设计流量不应小于消防给水系统官网的正常泄漏量，和系统自动启动流量；消防给水系统管网的正常池漏量应根据管道材质、接口形式等确定，当没有管网泄漏量数据时，稳压泵的设计流量宜按消防给水设计流量的1%-3%计，且不宜小于1L\u002Fs。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]