[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965154":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},965154,701,1,"单选题","气体灭火系统气压强度试验不符合规定的是：（ ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","试验前，必须用加压介质进行预试验，预试验压力宜为0.2MPa",false,{"key":16,"text":17,"correct":14},"B","试验时，应逐步缓慢增加压力，当压力升至试验压力的50%时，如未发现异状或泄漏，继续按试验压力的10%逐级升压，每级稳压3min，直至试验压力。保压检查管道各处无变形、无泄漏为合格",{"key":19,"text":20,"correct":14},"C","对气动管道，应取驱动气体储存压力",{"key":22,"text":23,"correct":24},"D","试验时，应以不大于0.5MPa\u002Fs的升压速率缓慢升压至试验压力，关断试验气源3min内压力下降不超过试验压力的10%为合格",true,"气体灭火系统气压强度试验应遵守下列规定：试验前，必须用加压介质进行预试验，预试验压力宜为0.2MPa。试验时，应逐步缓慢增加压力，当压力升至试验压力的50%时，如未发现异状或泄漏，继续按试验压力的10%逐级升压，每级稳压3min，直至试验压力。保压检查管道各处无变形、无泄漏为合格。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]