[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965019":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},965019,701,1,"单选题","关于灭火器结构检查的表述，不属于合格判定标定标准的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","灭火器开启机构灵活、性能可靠，可倒置开启和使用",true,{"key":16,"text":17,"correct":18},"B","提把和压把无机械损伤，表面不得有毛刺、锐边等影响操作的缺陷",false,{"key":20,"text":21,"correct":18},"C","灭火器头（阀门）外观完好、无破损",{"key":23,"text":24,"correct":18},"D","安装有保险装置，保险装置的铅封（塑料带、线封）完好无损","判定灭火器结构检查为合格要求的有： （1）灭火器开启机构灵活、性能可靠，不得倒置开启和使用；提把和压把无机械损伤。表面不得有毛刺、锐边等影响操作的缺陷 （2）灭火器器头（阀门）外观完好，无破损。并安装有保险装置。保险装置的铅封（塑料带、线封）完好无损。 （3）二氧化碳灭火器的阀门能够手动开启、自动关闭，其器头设有超压保护装置，保护装置完好有效。 （4）手提式灭火器装有间歇喷射机构《除二氣化碳灭火器以外的推车式灭火器的喷射软管前端。装有可间歇喷射的喷射枪，设有喷射枪夹持装置，灭火器推行时喷射枪不脱落。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]