[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-965007":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},965007,701,1,"单选题","可燃气体探测报警系统出现某一回路可燃气体探测器全部掉线故障，原因不可能是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","探测器供电线路短路或者断开",false,{"key":16,"text":17,"correct":14},"B","探测器通信线路短路或者断开",{"key":19,"text":20,"correct":21},"C","探测器反馈线路短路或者断开",true,{"key":23,"text":24,"correct":14},"D","该回路出现接地故障","某一回路可燃气体探测器全部掉线故障原因： （1）探测器供电线路短路或者断开 （2）探测器通信线路短路或者断开 （3）该回路出现接地故障 维修方法： （1）检查该回路供电\u002F通信连接线是否断开，连接好该回路供电\u002F通信连接线路 （2）用万用表检查探测器回路供电\u002F通信线路是否存在短路情况，排查短路故障 （3）利用兆欧表（揺表）检测该回路供电\u002F通信线路与大地之间的接地电阻。阻值小于产品说明书中的绝缘要求则为接地故障，利用分段法排查回路线路接地点并修复接地故障",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]