[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964929":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},964929,701,1,"单选题","消防水池进水管应根据有效容积和补水时间确定，补水时间不宜大于（ ）h。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","20",false,{"key":16,"text":17,"correct":14},"B","30",{"key":19,"text":20,"correct":21},"C","48",true,{"key":23,"text":24,"correct":14},"D","60","《消防给水及消火栓系统技术规范》4.3.3消防水池进水管应根据有效容积和补水时间确定，补水时间不宜大于48h。但当消防水池的总容积大于2000立方米时，不应大于96h。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]